9.4.2 MONITOR MENU
From the main menu, by holding down simultaneously for 2 sec the keys "SET" and "-", or using the selection menu
and pressing "+" or "-", you can access the MONITOR MENU.
In this menu, by pressing the MODE key, the following values are displayed in sequence.
FF: Fault log display
Chronological display of the faults that have occurred during system operation.
For each fault the following are displayed:
A symbol for the area concerned: the panel, pump P1 or pump P2.
The type of error or alarm, summed up in a code. See Table 19).
The number of times the error has occurred.
A text description of the error or alarm.
The time of switching on the panel or of pump operation at which the error occurred.
The order of the error in the log and the number of errors in the memory.
The faults are displayed in chronological order starting from the oldest one. The last one that occurred is shown first.
The maximum number of faults that can be displayed is 64; if the number of errors is greater, the oldest ones are
overwritten.
CT: Display contrast
Adjusts the display contrast.
LA: Language
Changes the language used on the display. Attention, Kiwa mode is present only if the language is Dutch, French or
English UK and US.
Note: If US is selected, the E.Box will use English with Imperial measurements.
HS: System operating hours
Indicates the hours the system has been on.
H1: Pump P1 operating hours
Indicates the hours the pump P1 has been on.
H2: Pump P2 operating hours
Indicates the hours the pump P2 has been on.
9.4.3 SETPOINT MENU
From the main menu, hold down simultaneously the "MODE" and "SET" keys until "SETPOINT MENU" appears on the
display (or use the selection menu pressing "+" or "-"). In this menu the parameters displayed depend on the type of
application.
SP: Setting the Set Point pressure (only in pressure boosting and in KIWA pressure boosting with
pressure sensor)
Pressure Set Point at which the E.Box keeps the plant under pressure.
RP: Setting the Pressure Differential (only in pressure boosting and in KIWA pressure boosting
with pressure sensor)
Pressure differential in which the E.Box panel maintains the pressure in the plant. See chapter on pressure boosting.
HC: Pump P2 starting level (only in drainage or filling with depth sensor)
Starting level of pump P2.
HB: Pump P1 starting level (only in drainage or filling with depth sensor)
Starting level of pump P1.
ENGLISH
Figure 59: Errors in the memory