Figure 2: E.BOx Plus Board - DAB E.Box Plus Instrucciones De Instalación Y Mantenimiento

Ocultar thumbs Ver también para E.Box Plus:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 308
Function
QS1
Supply line isolating switch (On the front panel of the e.box not shown in the figure)
L1 – L2 – L3
Three-phase power supply line connection
L – N
Single-phase power supply line connection
Earthing connection
U - V - W
Three-phase electrical connection of the pumps P1 and P2
L - N
Single-phase electrical connection of the pumps P1 and P2
C - A - P
Electrical connection for single-phase pumps P1 and P2 with external capacitor
Electrical connection for external starting capacitor for single-phase pumps with
C1 – C2
external capacitor. For P1 and P2. Basic version only.
Electrical connection for external starting capacitor for single-phase pumps with
A - P
external capacitor. For P1 and P2. Plus version only.
KK1- KK2
Thermal protection input for the motor of pumps P1 and P2
A-B-C
Terminals connecting digital inputs for level or pressure control