Activation Of The Set; Regulating The Rated Current Of The Pumps (Imax), Set Point (Sp) And Differential Restarting Pressure (Dp); Figure 15: Enabling P1 And P2; Figure 16: Regulating: Imax, Sp And Dp - DAB E.Box Plus Instrucciones De Instalación Y Mantenimiento

Ocultar thumbs Ver también para E.Box Plus:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 308

5.12 Activation of the set

To activate the set it is necessary to enable the pumps. During the first configuration, for safety's sake,
the pumps are disabled and are OFF. To change to automatic mode, just briefly press the
on the pumps P1 and P2. As shown in Figure 15 Enabling P1 and P2.
5.13 Regulating the rated current of the pumps (Imax), Set point (SP) and differential
restarting pressure (DP)
With a straight tip screwdriver, position the indices in the centre of the graduated scales, shown in Figure 16
Regulating: Imax, SP and DP, so that:
Imax indicates the rated current of the installed pumps, which you can find on the pump data plate.
SP indicates the desired set point pressure.
DP is the pressure variation, in percentage of the set point, necessary to restart the pumps.
Attention, the differential restarting pressure is calculated as SP * DP. If the set point is 4 bar and DP is 50%,
the pressure differential RP is 2 bar.
ENGLISH

Figure 15: Enabling P1 and P2.

Figure 16: Regulating: Imax, SP and DP

82
buttons

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

E.box plus dE.box basicE.box basic d

Tabla de contenido