TABELLA DEI PARAMETRI DI SET-UP
PARAMETRO
PARAMETER
PAR
Corrente primario T.A.
CT primary current
P.01
Primario TC
kvar step più piccolo
Smallest step kvar (lowest common multiple)
P.02
kvar paso más pequeño
Tensione nominale condensatori
Rated capacitor voltage
P.03
Tensión nominal condensador
Tempo di riconnessione
Reconnection time
P.04
Tiempo de reconexión
Sensibilità
Sensitivity
P.05
Sensibilidad
Coefficiente dello step 1
P.06
Step 1 coefficient
LED 1
Coeficiente paso 1
Coefficiente dello step 2
P.06
Step 2 coefficient
LED 2
Coeficiente paso 2
La programmazione dei rimanenti step, ad eccezione degli ultimi 2, avviene come i precedenti step 1 e step 2.
Follow the same programming as above for the first two steps except for the last two.
La programación para el resto de los bancos excepto los ultimos 2, se realiza como los precedentes step 1 y step 2.
Coefficiente penultimo step
P.06
LED ...❶
Second last step cefficent
Coeficente penúltimo step
Coefficiente ultimo step
P.06
LED ...❶
Last step cefficent
Coeficente último step
Impostazione del cosϕ desiderato ❸
Setting of required cosϕ value ❸
Set-point del cosϕ deseado ❸
n = Numero di step dell'apparecchio.
= Contatto aperto in assenza di allarme.
noA
= Contatto chiuso in assenza di allarme.
ncA
= Comando ventilatore.
FAn
Vedere a pagina 6 il capitolo visualizzazione delle
misure e impostazione del cosϕ.
DESCRIZIONE DEI PARAMETRI SET-UP
BASE
P.01 - Corrente primario T.A.
Corrente primaria del TA.
P.02 - kvar step più piccolo
Potenza nominale in kvar della batteria più
piccola installata.
Esempio: 10 kvar impostare
10.00
P.03 - Tensione nominale condensatori
Tensione nominale (di targa) dei
condensatori.
Esempio: 440V impostare
0440
P.04 - Tempo di riconnessione
Tempo minimo necessario alle batterie per
scaricarsi e poter essere utilizzate di nuovo.
Esempio: 60 sec impostare
0060
P.05 - Sensibilità
La sensibilità é un coefficiente che permette
di regolare la velocità di intervento del
regolatore. Con sensibilità bassa si hanno
regolazioni più veloci ma un numero di
inserzioni più elevato, mentre con sensibilità
alta la regolazione sarà più lenta ma verranno
risparmiate manovre.
TABLE OF BASE MENU PARAMETERS
DESCRIZIONE
DESCRIPTION
FUNCIÓN
n = Number of controller steps
= Normally open contact in no alarm
noA
conditions
= Normally closed contact in no alarm
ncA
conditions.
= Fan control
FAn
See Measurement and cosϕ setting section on
page 6.
DESCRIPTION OF BASE MENU
PARAMETERS
P.01 - CT primary current
CT primary current.
P.02 - Smallest kvar step
Rated power in kvar of the smallest installed
capacitor bank.
Example: For 10 kvar, set
10.00
P.03 - Rated capacitor voltage
Rated voltage (nameplate) of the capacitors.
Example: For 440V, set
0440
P.04 - Reconnection time
Minimum time needed for the capacitor to
discharge and be ready to used again.
Example: For 60 seconds, set
0060
P.05 - Sensitivity
The sensitivity is a coefficient, which
consents to adjust the controller tripping
speed. A low sensitivity provides for faster
adjustments but with a greater number of
switchings. With high sensitivity, the
adjustment is slower but with fewer
switchings.
TABLA DE PARAMETROS MENÙ BASICO
n = Numero de paso del regulador.
= Contacto abierto en ausencia de alarma.
noA
= Contacto cerrado en ausencia de
ncA
alarma.
= Comando ventilador
FAn
Ver sección medición y ajuste des cosϕ en la
página 6.
DESCRIPCIÓN DE LOS PARÁMETROS DEL
MENU BASICO
P.01 - Corriente primario TC
Corriente primaria del TC.
P.02 - Kvar paso mas pequeño
Potencia nominal en Kvar del paso mas
pequeño instalado.
Ejemplo: Para 10 kvar, ajustar
10.00
P.03 - Tensión nominal de condensadores
Tensión nominal (de placa) de los
condensadores.
Ejemplo: Para 440V, ajustar:
0440
P.04 - Tiempo de reconexión
Tiempo mínimo necesario para la descarga
del condensador y la reconexión del mismo.
Ejemplo: Para 60 segundos, ajustar
0060
P.05 - Sensibilidad
La sensibilidad es un coeficiente que permite
regular la velocidad de intervención del
regulador. Con un valor de sensibilidad baja
se logra una compensación rápida, pero con
un mayor numero de conmutaciones. Con una
sensibilidad alta la compensación es lenta,
pero con pocas conmutaciones de pasos.
RANGE
DEFAULT
RANGE
DEFAULT
RANGO
DEFAULT
OFF ...10.000
OFF
0.10...300
1.00
80...750V
400
5...240sec
60
5...600sec
60
0...16
0
0...16
0
0...16
0
noA
ncA
FAn
0...16
0
noA
ncA
FAn
0.80Ind...0.80Cap
0.95Ind
3