Site Selection and Preparation
Section 3
3.1 — Site Selection
Clearance from operable
windows, doors or any
openings in the wall.
These guidelines are based upon fire
testing of the generator enclosure and
the manufacturer's requirement for air
flow for proper operation. Local codes
may be different and more restrictive
than what is described here.
60 in (1524 mm) Minimum
Installation Guidelines for Air-Cooled Generators
No operable windows or openings in the wall permitted
within 5 ft (1.52 m) from any point of the generator.
Existing Wall
60 in (1524 mm)
Minimum Distance
36 in
(914 mm)
Generator
Figure 3-1. Installation Guidelines
18 in (457 mm)
60 in (1524 mm)
Top of Generator
Clearance from the ends and front of the gener-
ator must be 36 in (914 mm). This would
36 in
include shrubs, bushes or trees. Clearance at
(914 mm)
the top should be a minimum of 60 in (1524
mm) from any structure, overhang or projec-
tions from the wall. The generator should not
be placed under a deck or other structure that
is closed in and would limit or constrain air flow.
60 in (1524 mm)
Required
Minimum From Ends
to openings in walls
Clearance from operable
36 in
windows, doors or any
(914 mm)
openings in the wall.
18 in (457 mm)
Minimum
13