Installation
Figure 1 – Operating Window
5/16 - 18 UNC X 1/2 DEEP
3 1/2 NH
THREAD
120°
2-1/2
5-11/16
5-31/64
2-1/4
21-7/16
14-15/16
45°
14-5/8
11-9/16
4-1/2
R6
4-1/2
5-1/2
4-15/32
5-9/16
SWING RADIUS
12-7/16
Mechanical Monitor Attachment
The monitor is to be mounted on a waterway which is capable of withstanding the pressure applied to the monitor as well as the
reaction force and resulting bending moment of the nozzle (1700 lbs at 250 PSI and 2000 GPM) .
Insufficient structural support at the inlet flange can lead to failure, which has potential to cause an injury .
Use 5/8" bolts and nuts of grade five minimum . Use suitable washers with a minimum of six thread engagements . Use a ring gasket
conforming to ASME 16 . 2 1 . The control box is considered the front of the monitor . Use Figure 1 to position the monitor to function
within the desired operating window .