Descargar Imprimir esta página

Valve System; Transition Plate; Valve Zone; Base Plates - Emerson AVENTICS EtherCAT Descripción De Sistema

Acoplador de bus aes/controladores de válvula av

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 84
The assembly of the components and the complete unit is described in
the respective assembly instructions. All necessary assembly instruc-
tions are included as printed documentation on delivery and can also
be found on the CD R412018133.

12.1 Valve system

The AV series valve system consists of a central bus coupler that can be extended
towards the right to up to 64 valves and up to 32 associated electrical compo-
nents (see "Impermissible configurations"). Up to 10 input and output modules
can be connected on the left side. The unit can also be operated without pneu-
matic components, i.e. with only a bus coupler and I/O modules, as a stand-alone
system.
Fig. 10 shows an example configuration with valves and I/O modules. Depending
on the configuration, your valve system may contain additional components,
such as pneumatic supply plates, electrical supply plates, or pressure regulators
(see "Valve zone").
29
28
27
26
Fig. 9: Example configuration: unit consisting of AES series bus coupler and I/O
modules, and AV series valves
26
Left end plate
27
Bus coupler
28

Pneumatic supply plate

29
Right end plate
30
Electrical unit, AES series

12.2 Valve zone

The following figures show the components as illustrations and sym-
bols (see "Conversion of the valve zone").

12.2.1 Base plates

The valves from the AV series are always mounted on base plates that are assem-
bled into blocks so that the supply pressure is applied to all valves.
The base plates are always 2x or 3x base plates for two or three single or double
solenoid valves.
AVENTICS™ EtherCAT | R412018142-BAL-001-AG | English
32
30
34
35
32
I/O modules
33

Transition plate

34
Valve driver (concealed)
20
20
35
Pneumatic unit, AV series
33
Fig. 10: Base plates, 2x and 3x
(1)
Valve position 1
(3)
Valve position 3
21
21 Base plate, 3x
12.2.2 Transition plate
The transition plate (29) has the sole function of mechanically connecting the bus
coupler to the valve zone. It is always located between the bus coupler and the
first pneumatic supply plate.
Fig. 11: Transition plate
12.2.3 Pneumatic supply plate
Pneumatic supply plates (30) can be used to divide the valve system into sections
with different pressure zones (see "Conversion of the valve zone").
Fig. 12: Pneumatic supply plate

12.2.4 Electrical supply plate

The electrical supply plate (36) is connected to a supply board. It can feed in an
extra 24 V power supply for all valves located to the right of the electrical supply
plate via an integrated 4-pin M12 connection. The electrical supply plate moni-
tors the additional power supply (UA) for low voltage.
20
21
(2)
Valve position 2
20
20 Base plate, 2x
29
30
20
21
29
30
P
34

Publicidad