3.8.2
Diagnostic leds (Diag Leds).
The diagnostic leds are sub
divided as follows:
Bus: field bus (DeviceNet)
diagnosis.
PLC: PLC
diagnosis.
I/O: K-bus diagnosis.
The leds can be off, green, orange or red.
After switching on, the Bus Terminal Controller
immediately checks the connected configuration.
−
the I/O led goes out if the start-up was
successful.
−
a red I/O led indicates a Bus Terminal
Controller error. The error type is shown in the
display.
3.8.3
Leds for field bus diagnosis.
Led Bus
GB
Off
Red fixed
Red
flashing
Orange
flashing
Green
flashing
Green
fixed
3.8.4
Led for PLC diagnosis.
Led Plc
Off
Red
flashing
Red fixed
Orange
fixed
Green
fixed
20
(BX5200)
Description
No field bus connected.
No
field
bus
connected.
DeviceNet 24V absent.
Communication
error.
Time
out
DeviceNet
communication.
Baud rate search active, no
baud rate found.
No communication to the
DeviceNet master.
DeviceNet
communication
active.
Description
Plc in stop or no program
available.
The set task time is
sometimes exceeded.
The set task time is always
exceeded.
Plc runs without boot project
(only lights up during cycle),
when the boot project is
generated, the led orange
flashes.
Boot project – Plc is running
(only lights up during cycle).
3.8.5
Led for K-Bus diagnosis.
Led IO
Off
Red fixed
Orange
fixed
Green
fixed
3.8.6
Diagnostics display.
During start-up, display shows the current
firmware version for 3 seconds.
If an error occurs during start-up, this will be
indicated via a flash sequence of the associated led.
Configuration errors are shown in the display via
"TC-Config" and an error number.
In this case, use the System Manager to check
hardware configuration or contact support.
Display
IO
TC-
Config.
0xF0nn
Firmware errors are shown in the display via FW-
Error and an error number.
Display
FW-Error
0xnnnn
3.9
K-Bus diagnostic Error Codes.
To visualize an K-Bus Error Code:
− press for 3 seconds the
Joystick
to
BX5200
module
Menu (see figure);
− press the Joystick in Left
or
Right
navigate the Setup Menu
until reach the K-Bus
Menu, indicated on BX5200 module display;
− the indication of eventual Error Code is
visualized on display;
− the meaning of Error Codes is indicated in table
3.9.1.;
− to exit the Setup Menu press for 3 seconds the
Joystick.
Description
No data are exchange via the
K-Bus.
Error flashing – error type –
display.
Register or KS2000 online
access.
K-Bus OK and Running.
Description
Bus Terminal no. nn does not
correspond to the
configuration. Compare bus
structure of Bus Terminal no.
nn with the configuration.
Description
Please contact support.
enter
the
Setup
position
to