Start-up
Checking and settings
Combustion components and secondary air
5
5
Checking and setting combustion
components
Burner is supplied already set for
natural gas.
· Remove safety screw D.
· Remove mobile spindle E.
· Open burner body.
· Disconnect both ignition cables.
· Remove hose from hydraulic
distributor.
· Loosen by two turns all four screws
1 of RTC plate.
· Loosen nut and side screw C
retaining gas and fuel oil feed line.
· Take out combustion components.
· Check settings of the following :
ignition electrodes and diffusers
according to available gas and
diagrams opposite.
· Adjust and place nozzle according to
boiler capacity.
· Check that O-ring J1 is in correct
position on gas feed line.
· Reassemble unit.
· Check the following :
– tightness of screw, of nut C, and
also of the hose's nut.
– possible leaks.
Each valve function is engraved on
distributor body, therefore: S, 1, 2, 3.
Electrical connections are called VS,
5
S1, S2, S3.
S+VS = Y17 Safety valve
1+S1 = Y1 Ignition and 1
nd
2+S2 = Y2 2
rate valve
rd
3+S3 = Y3 3
rate valve and nominal
4
power
1
Four screws to take out the
combustion components.
5
2
Two screws to set dimension Y
L
Value of secondary air.
05/2006 - Art. Nr. 13 013 500B
Secondary air
This is the amount of air flowing
between the turbulator diameter and
blast-tube. Turbulator position
(dimension Y) is read on the 0 to 50mm
graduated scale of the RTC
(Maintained head settings)-system.
Maximum secondary air is set at 50
and minimum at 0.
On delivery, dimension Y is set at 20 or
30mm (see table).
However, this value can be adjusted
according to the following :
firing quality (shock, vibration,
judder, time lag),
combustion quality.
Setting
This is performed without removing
burner, whether stopped or in
operation, according to enclosed
values.
By reducing dimension Y, CO
increases and vice versa.
· Loosen both screws 2 (diagram).
· Slide unit in chosen direction.
· Retighten both screws 2.
Dual fuel
type
C120
C160
C160
C210
Highlighted : equipment on delivery
st
rate valve
EN
2
Burner
Dimension
power kW
Y mm
700
0
900
10
1100
20
1200
25
1100
20
1300
30
1600
50
1150
10
1400
20
1700
30
1900
40
2050
50
33