Menu 6 Radio settings
Programming the hand-held radio transmitter
Please observe that every hand-held transmitter must be pro-
grammed individually.
The following encryption types can be programmed: KeeLoq, 12
Bit Multibit. The first code programmed determines the encryption
type.
Start pulse (menu item 60)
1.
Select "Program hand-held transmitter start button" in menu
item 60.
2.
Actuate the button of the hand-held transmitter for opening
the door.
ð
When the code has been programmed, the dot display
on the LED display blinks 5 times.
3.
Go to Exit to complete the setting process.
Light function (menu item 62)
Select menu item 62 and actuate the light function button of the
hand-held transmitter. When the code has been programmed, the
dot display on the display blinks 5 times.
Deleting radio codes (menu item 63)
To delete all codes programmed, proceed as follows:
1.
Select menu item 63.
2.
Press and hold the
When all codes have been deleted, the dot display on
the display blinks 5 times.
Menu 7 DU settings
DU functions
At initial operation, the control must be reset to default settings in
menu item 99. The "Opening force limitation" function in the DU
can be selected in menu 4 under menu item 48:
Value = 0
Force limitation off
Value = 1 - 99 Force limitation is active
Protecting the drive against overheating
NOTICE
In order to protect the drive against overheating,
the duty cycle must be set to the value 5 in
menu 4 under menu item 49.
Menu area 71-78 is automatically enabled if a drive with DU func-
tion has been detected.
Wireless RadioBand closing edge
Prior to every operational cycle, the RadioBand system checks
the system function by a test signal and complies with PL c as per
EN 13849-1.
Insert the module to J14 and select the value 4 in menu item 35
and the value 5 in menu item 53. The function of terminal J3 is
disabled. Also follow the directives given in the instructions for the
RadioBand.
Crush hazard and risk of being struck by the
WARNING
closing door
Observe that sensors connected to J3 do not
have any function.
Test run
When programming has been completed, carry out a test run by
executing all operating functions. If all operating functions can be
carried out correctly, the connected door system and loading
bridge is ready for operation.
button for 5 seconds.
6
Program overview
Menu 1 Basic settings loading bridge
menu
Entry
item
10
Overcurrent hydraulic pump
0-3
4-6
7-8
9-12
13
Automatic time
0 - 3
4 - 6
7 - 9
14
Automatic retraction
0
1 - 4
5 - 8
9 -10
15
Connection J6: Wheel chock / resting position
0
1
17
Combined operating modes
0
1
2
3
4
5
- -
Menu 2 door sealing
Menu
Entry
item
20
Door sealing
0
1
2
21
Switch-off delay
0
1 - 6
7 - 12
22
Switch-on delay
0
1-6
7-12
- -
TAD MS 400V / 230V
Selection
0 = 0.0 A / 1 = 2.6 A / 2 = 3.2 A / 3 = 3.8 A
4 = 4.4 A / 5 = 5.0 A / 6 = 5.6 A
7 = 6.2 A (default setting) / 8 = 6.8 A
9 = 7.4 A / 10 = 8.0 A / 11 = 8.6 A / 12 = 9.2 A
0 = 3 s / 1 = 5 s / 2 = 7 s / 3 = 9 s
4 = 11 s / 5 = 13 s (default setting) / 6 = 15 s
7 = 20 s / 8 = 25 s / 9 = 30 s
Off (default setting)
1 = 0.2 s ; 2 = 0.4 s ; 3 = 0.6 s ; 4 = 0.8 s
5 = 1.0 s ; 6 = 1.2 s ; 7 = 1.4 s ; 8 = 1.6 s
9 = 1.8 s ; 10 = 2.0 s
without function (default setting)
with wheel chock
mutual locking of door – loading bridge
without locking of door – loading bridge
locking of door – loading bridge without
sensor
locking of loading bridge with door not opened
only loading bridge operation (default setting)
only door operation
Exit menu
Selection
off (default setting)
on
reserved
0 s (default setting)
5 s / 10 s / 15 s / 20 s / 25 s / 30 s
35 s / 40 s / 45 s / 50 s / 55 s / 60 s
0 s (default setting)
5 s;10 s;15 s;20 s;25 s;30 s;
35 s;40 s;45 s;50 s,55 s;60 s
Exit menu
EN - 29