Troubleshooting - Novoferm tormatic TAD MS 400V Manual De Instrucciones Y De Montaje

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 62
Radio hand-held transmitter (optional)
Start button (functional process in pulse OPEN operating mode /
pulse CLOSE):
Initial pulse generation:
Drive starts and moves the door to the end position OPEN
or CLOSE that is set.
Pulse generation during the process:
Door stops.
New pulse:
Door continues moving in the opposite direction.
Light button:
The light function is a continuous light, which can be
switched irrespective of the "ON / OFF" door action.
Key switch function (optional)
The control is provided with an input for a key switch. This allows
you to activate various functions using menu item 50, "Key switch
function".
Door action status display
Display State
Upper end position OPEN reached
Door end position has not been reached
Lower end position CLOSE reached
Representation of the door opening frequency
Representation of the door closing frequency
Decommissioning of the loading bridge
1.
Press the RETURN or AUTO button to move the loading
bridge back into resting position.
2.
Set the main switch to the "0" (Off) position.
3.
Secure the main switch against switching-on.
34 - EN
8

Troubleshooting

Error
State
E02
Door neither opens
nor closes. Safety in-
put J4.3/4 triggered
E03
Door neither opens
nor closes. Wicket
door open
E05
Door neither opens
nor closes. Safety
switch has triggered
E06
Door reverses / does
not close
E07
Door reverses / does
not close
E08
Door neither opens
nor closes. DES
safety circuit drive
open
E09
Door neither opens
nor closes
E10
Menu item 36 set to
value 3 or 4
E11
Door neither opens
nor closes. Slack
rope switch has
triggered
E91
Door neither opens
nor closes. Continu-
ous STOP command
detected
F01
No door movement
F2
No response
F3
F4
F5
Reset has been ex-
ecuted
F09
Hydraulic motor
switches off
F10
Door stops shortly
after start command
F11
Short circuit at
valve 1
F12
Short circuit at
valve 2
F14
Interruption at valve 1 Valve 1: check supply line.
F15
Interruption at valve 2 Valve 2: check supply line.
F17
Loading bridge is not
responding.
F19
Door responds only to
dead man's control
for closing
TAD MS 400V / 230V
Diagnosed cause
Check status of the peripherals at
J4.3/4.
Close wicket door.
Connection line 8k2 strip dam-
aged, check slack rope switch.
Closing edge has triggered.
Check menu item 35.
Photoelectric sensor has
triggered. Check menu item 36.
Manual override actuated, Motor,
thermal switch has triggered, mo-
tor overload or blockage.
No door end position pro-
grammed.
Program door end position under
menu items 30 + 31.
Completely open and close door
to determine the position of the
photoelectric sensor.
Check ropes.
Check STOP button at J1. Stop
membrane key actuated.
Faulty feedback for brake relay.
Error occurred during self-testing.
Replace control.
Check mains environment with
regard to electrical disturbance
sources, increase distance of mo-
tor cable and / or signal lines to
mains cables, actuate start button
on control for normal operation.
The power control of the motor
pump has tripped. Check menu
setting 10.
Check loading bridge for ease of
motion.
Fault in the control electronics.
Exchange control.
Valve 1, check supply line.
Valve 2, check supply line.
Fault on hydraulic motor control.
Closing edge testing has failed.
Check closing edge safety
device.