Descargar Imprimir esta página

Toshiba RAV-GM901BTP-E Manual De Instalación página 27

Ocultar thumbs Ver también para RAV-GM901BTP-E:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 118
Wired
Wireless remote
remote
controller Sensor block
controller
display of receiving unit
display
Main problem parts
Operation Timer
Indication
Ready
Flashing
GR GR OR
P07
ALT
Heat sink overheat
Indoor unit water
P10
ALT
overflow detected
The fan error of the
P12
ALT
indoor unit
Gas leakage
P15
ALT
detected
P19
ALT
4-way valve error
High-pressure
P20
ALT
protective operation
P22
ALT
Outdoor unit fan error
Outdoor unit inverter
P26
ALT
Idc activated
Outdoor unit position
P29
ALT
error
Other indoor unit
P31
ALT
error
: Lighting
: Flashing
: OFF
: The air conditioner automatically enters the auto-address setting mode.
ALT : When two LEDs are flashing, they flash alternately. SIM: When two LEDs are flashing, they flash in synchronization.
Receiving unit display OR : Orange GR : Green
51-EN
Judging
Parts to be checked / error description
device
Abnormal temperature was detected by the temp,
Outdoor
sensor of the IGBT heat sink.
Drain pipe, clogging of drainage, float switch
Indoor
circuit, indoor P.C. board --- Drainage is out of
order or the float switch was activated.
Abnormal operation of the indoor fan motor, indoor
P.C. board, or indoor DC fan (over current or lock,
Indoor
etc.) is detected.
External static pressure setting error.
There may be gas leakage from the pipe or
Outdoor
connecting part. Check for gas leakage.
4-way valve, indoor temp, sensors (TC / TCJ) ---
Outdoor
An error was detected due to temperature drop
(Indoor)
of the indoor unit heat exchanger sensor when
heating.
Outdoor
High-pressure protection
Outdoor unit fan motor, outdoor unit P.C. board ---
Outdoor
An error (overcurrent, locking, etc.) was detected in
the outdoor unit fan drive circuit.
IGBT, outdoor unit P.C. board, inverter wiring,
compressor --- Short-circuit protection for
Outdoor
compressor drive circuit devices (G-Tr / IGBT) was
activated.
Outdoor unit P.C. board, high-pressure switch ---
Outdoor
Compressor motor position error was detected.
Another indoor unit in the group is raising an alarm. Entire stop
Indoor
E03 / L07 / L03 / L08 alarm check locations and
error description
Air
conditioner
status
Entire stop
Entire stop
Entire stop
Entire stop
Auto-reset
Entire stop
Entire stop
Entire stop
Entire stop
Auto-reset
– 26 –