Warning! Qualified Technician Required for Service and Installation
Basic Installation and Configuration Guidelines
Use minimum 6AWG copper conductors only.
Torque fi eld connections between 21 and 23 in lbs.
Readily accessible disconnecting means to be provided at time of
installation.
Permanently connected.
Connect only to a circuit protected by a Class A Ground Fault
Circuit Interrupter (GFCI) or Residual Current Device (RCD)
mounted at least 5' (1.52M) from the inside walls of the spa/hot tub
and in line of sight from the equipment compartment.
CSA enclosure: Type 2
Refer to Wiring Diagram inside the cover of the control enclosure.
Refer to Installation and Safety Instructions provided by the spa
manufacturer.
Warning: People with infectious diseases should not use a spa or
hot tub.
Warning: To avoid injury, exercise care when entering or exiting
the spa or hot tub.
Warning: Do not use a spa or hot tub immediately following
strenuous exercise.
Warning: Prolonged immersion in a spa or hot tub may be inju-
rious to your health.
Warning: Maintain water chemistry in accordance with the Manu-
facturers instructions.
Warning: The equipment and controls shall be located not less
than 1.5 meters horizontally from the spa or hot tub.
Warning! GFCI or RCD Protection.
The Owner should test and reset the GFCI or RCD on a
regular basis to verify its function.
Warning! Shock Hazard! No User Serviceable Parts.
Do not attempt service of this control system. Contact your
dealer or service organization for assistance. Follow all
owner's manual power connection instructions. Installation
must be performed by a licensed electrician and all grounding
connections must be properly installed.
32
CSA Compliance/Conformité
Caution:
• Test the ground fault circuit interrupter or residual current device
before each use of the spa.
• Read the instruction manual.
• Adequate drainage must be provided if the equipment is to be
installed in a pit.
• For use only within an enclosure rated CSA Enclosure 3.
• Connect only to a circuit protected by a Class A ground fault
circuit interrupter or residual current device.
• To ensure continued protection against shock hazard, use only
identical replacement parts when servicing.
• Install a suitably rated suction guard to match the maximum fl ow
rate marked.
Warning:
• Water temperature in excess of 38°C may be injurious to your
health.
• Disconnect the electrical power before servicing.
• Disconnect the electric power before servicing. Keep access door
closed.