Dual pump function/Y-pipe
application
Fig. 13: Example, differential pressure sen-
sor connection
InterFace-Module (IF-Module)
74
NOTE:
The properties described below are only available if the internal MP
interface (MP = Multi Pump) is used.
• Both pumps are controlled by the master pump.
If one of the pumps malfunctions, the other will run according to the
master's control settings. In case of a total failure of the master, the
slave pump operates at emergency operation speed.
The emergency operation speed can be set in menu <5.6.2.0>
(see chapter 6.3.3 on page 76).
• The master's display will show the status of the double pump. On the
slave display, 'SL' will appear.
• In the example in Fig. 13, the master pump is the left-hand pump in the
direction of flow. Connect the differential pressure sensor to this pump.
The measuring points of the differential pressure sensor of the master
pump must be on the suction and pressure side of the double-pump
system in the corresponding collector pipe (Fig. 13).
For communication between pumps and the building management
system, one IF-Module (accessories) is required. This is plugged into
the terminal space (Fig. 1).
• The master-slave communication uses an internal interface (terminal:
MP, Fig. 25).
• Normally for double pumps, only the master pump must be equipped
with an IF-Module.
• For pumps in Y-pipe applications in which the electronic modules are
connected to each other through the internal interface, only the mas-
ter pumps require an IF-Module.
Communication
PLR/Interface converter
LONWORKS network
BACnet
Modbus
CAN bus
Table 2: IF-Modules
NOTE:
The procedure and further information for commissioning and con-
figuring the IF-Module on the pump can be found in the installation
and operating instructions of the IF-Module used.
Master pump
Slave pump
IF-Module PLR
No IF-Module
necessary
IF-Module LON
No IF-Module
necessary
IF-Module BACnet No IF-Module
necessary
IF-Module Modbus No IF-Module
necessary
CAN IF-Module
No IF-Module
necessary