Technical data

3.1

Electrical data

AC supply voltage
see type plate
AC current consumption
see type plate
Nominal DC battery voltage
see type plate
DC charge current
see type plate
Power supply output
Output factor under normal conditions
Short-circuit-proof
Reverse polarity protection
Excess temperature protection class
Excess voltage category
Contingent dimensioning short circuit current I
Minimum required short circuit current
Degree of disruption
An all-current sensitive version must be installed when using residual
current devices (Ia = 30 mA).
3.2

Ambient conditions

Place of use
Ambient storage temperature
Ambient temperature for activation
Ambient temperature for operation
Relative humidity
Dusty environments
Protection against contact, dust
3.3
Installation
Position the charger on a firm, level surface. The flow of air through the
openings on the underside of the device to the rear side must not be
obstructed.
When installing the charger, make sure that there is a clearance of at least
5 cm to the left, right, and rear of the device in order to ensure adequate
ventilation.
Always install the device at a higher level than the top edge of the battery.
In dusty environments, the charger must always be mounted on the wall
and a dust filter must be used.
Only suitable for installation on concrete or another non-flammable
surface.
Operation in the packaged state is never permissible. The sole exclusion
is brief commissioning of the device under constant observation by a
qualified person.
3.4
Small housing:
3~ 400..480 V/50..60 Hz
I
5..29.9 A per phase
max
and depending on design
24..80 V
depending on design
I
30..325 A
max
depending on design
P
3.3..17.2 kVA
max
approx. 0.97
Yes
Medium-sized housing:
Yes
1
2
:1 kA
CC
I
: 30 A
CP, mr
2
In dry, well-ventilated
areas up to at most
1.000 m above sea level
-25..+60 °C
0..+40 °C
-5..+40 °C
Max. 90 % (at 23 °C)
Exclusively with a filter
(accessory)
IP 21 and water
Example of type plate affixed on the right
Dimensions and type plate
19