Descargar Imprimir esta página

HOPPECKE trak HF premium Manual De Instrucciones página 27

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 95
9
Faults
Should there be a problem with your charger, you can find information
about the cause and possible remedial actions here.
Please have the following information ready if you would like to report
a fault (it can be found on the device's type plate):
Type designation and serial number of the affected charger
9.1
Information
Code
Name
CGH_I001
ManualStop
CGH_I002
PilotStop
9.2
Warnings
Code
Name
CHG_W001
TemperaturePowerModule
CHG_W002
ComWarningPowerModule
CHG_W003
ComWarningStatusBoard
CHG_W004
SDCardAlmostFull
CHG_W007
HardwarePowerModule-
Warning
CHG_W008
MissingSDCard
CHG_W009
PowerLoss
CHG_W010
TemperatureBattery
CHG_W011
ElectrolyteWarning
CHG_W012
PlugWearWarning
CHG_W013
TrakAirPressureHighWarning Pressure too high
CHG_W014
TrakAirPressureLowWarning
CHG_W015
TrakAirLeakageHighWarning After deactivating trak | air the
CHG_W016
ComTrakCom
CHG_W018
Please also note the following before making contact:
Description
Consequence/action
STOP button actuated during
Charge interruptions result in defective charging and without electrolyte
charging
circulation to battery damage. Wait until charging has ended and Complete
is illuminated.
Contact lost during charging
Charge interruptions result in defective charging and without electrolyte
in pilot function
circulation to battery damage. Wait until charging has ended and Complete
is illuminated.
Description
Consequence/action
Temperature issue in the
Overheating of the charger and loss of charge current. Please review the
power module
ventilation and ambient temperature with respect to proper use.
Power module
Device may stop charging. Please notify the HOPPECKE service technician.
communication fault
Status board
Device may stop charging. Please notify the HOPPECKE service technician.
communication fault
The SD card is 99 % full
Device may stop charging. Please notify the HOPPECKE service technician.
Power module
N/A
hardware fault
No memory card available
Defective memory card, charging continues as normal.
Although data will no longer be recorded.
Loss of mains power
One phase of the AC voltage supply is absent in the case of three-phase
devices. Please have an electrician inspect the mains supply.
Battery interface reports:
The connected battery is no longer being used correctly and will wear out
Battery very hot (> 55 °C)
and fail prematurely.
Please use a replacement battery.
Battery interface reports:
The electrolyte level in the connected battery is too low and will lead to
Low electrolyte level at start
direct, irreversible capacity loss.
of charging
Please fill with demineralised water.
Warning of plug wear
The configured threshold has been exceeded.
Replace plug and reset counter.
trak | air is deactivated. Check the pump.
Pressure too low
trak | air is deactivated. Check the pump.
Wait for 60 seconds. Check the pump.
pressure alteration per time
is too high
Values outside of tolerance
Restart the system.
Service interval will soon
Please notify the HOPPECKE service technician.
expire
What is being shown on the display? Is there a warning or fault
signal? Have you already read the error text?
When did you notice the error message?
When was the charger commissioned?
Where is the charger being used?
Who is the contact person in your company?
27