Maintenance
Venting engines with fuel shut-off valve connected
to supply voltage during operation:
Yes
Disconnect the connector at the oil pressure
switch.
SB= black
BL-W= blue-white
Is the engine equipped with a Volvo Penta in-
strument box?
Yes
Engines with a Volvo Penta instrument
box
1. If there is a coolant level alarm – check the
level. If the level is too low, the level alarm
stops the engine.
2. Briefly press the "Starter button". The instru-
mentation is now activated and the charge
lamp lights. If there is a coolant level
alarm: Hold in the "Interlock button" for ap-
proximately 4 seconds.
3. Vent the fuel system according to the in-
structions on the previous page.
4. Press the "Stop button"
5. Reconnect the connector
6. The engine is now operational
36
Is there "automatic stop in the event of too low oil
pressure" with a Volvo Penta oil pressure switch?
When the engine is off, this switch is closed ("Nc"-
Normally closed).
Is there "automatic stop in the event of too low
oil pressure" with a non-Volvo Penta oil pres-
sure switch that is open when the engine is off.
("No" = Normally open)
Short-circuit the connector for
the oil pressure switch with a
loop.
No
Engines with ignition switch
1. Turn the ignition switch to operating posi-
tion / ignition. In Volvo Penta ignition
switch position 1 (15+)
2. The solenoid valve is now activated for op-
eration (not stop position)
3. Vent the fuel system according to the stand-
ard procedures (see the previous page).
4. The engine is now operational
No
Yes