Section 3
Electrical Service Requirements (Global voltage chillers):
ThermoFlex7500/10000
ThermoFlex7500/10000
Electrical Service Requirements (High temperature chillers):
* Refer to Appendix A for country specific ratings.
3-6
ThermoFlex
Voltage ±10%
(Air-cooled)
400 VAC P 2 Pump
400 VAC P 3 Pump
400 VAC P 5 Pump
400 VAC T 5 Pump
460 VAC P 2 Pump
460 VAC P 3 Pump
460 VAC P 5 Pump
460 VAC T 5 Pump
Voltage ±10%
(Water-cooled)
400 VAC P 2 Pump
400 VAC P 3 Pump
400 VAC P 5 Pump
400 VAC T 5 Pump
460 VAC P 2 Pump
460 VAC P 3 Pump
460 VAC P 5 Pump
460 VAC T 5 Pump
ThermoFlex1400
Voltage ±10%
200 VAC 1KW
200-230 VAC 1KW
200 VAC 2KW
208-230 VAC 2KW
230 VAC 2KW
230 VAC 1KW
ThermoFlex2500
Voltage ±10%
200 VAC P 1 P 2 Pump
208-230 VAC P 1 P 2 Pump
208-230 VAC T 1 Pump
200 VAC T 1 Pump
Frequency
50 Hz
50 Hz
50 Hz
50 Hz
60 Hz
60 Hz
60 Hz
60 Hz
Frequency
50 Hz
50 Hz
50 Hz
50 Hz
60 Hz
60 Hz
60 Hz
60 Hz
Frequency
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
50 Hz
Frequency
50 Hz
60 Hz
60 Hz
50 Hz
230 VAC
50 Hz
Phase
MCA
MOPD
3Ø
8.8
15
3Ø
10.1
20
3Ø
12.3
20
3Ø
9.1
15
3Ø
8.8
15
3Ø
10.1
20
3Ø
12.3
20
3Ø
9.1
15
Phase
MCA
MOPD
3Ø
8.4
15
3Ø
9.7
20
3Ø
11.9
20
3Ø
8.8
15
3Ø
8.4
15
3Ø
9.7
20
3Ø
11.6
20
3Ø
8.8
15
Phase
Branch Circuit
Requirements
1Ø
20A
1Ø
20A
1Ø
30A
1Ø
30A
1Ø
32A
1Ø
*16A
, 15A
, 13A
1
2
Phase
Branch Circuit
Requirements
1Ø
30A
1Ø
30A
1Ø
30A
1Ø
40A
1Ø
32A
Continued on next page.
Line Cord
Plug
Hard wire
Hard wire
Hard wire
Hard wire
Hard wire
Hard wire
Hard wire
Hard wire
Line Cord
Plug
Hard wire
Hard wire
Hard wire
Hard wire
Hard wire
Hard wire
Hard wire
Hard wire
Line Cord
Plug
6-20P
6-20P
6-30P
6-30P
-
-
3
Line Cord
Plug
6-30P
6-30P
6-30P
Hard wire
-
Thermo Scientific