Electrical Connections

Main AC Wiring

NOTE: Main AC wiring must be in accordance with local
jurisdiction and codes.
1. Strip the insulation off the wire ends. Do not
remove excessive insulation.
2. Remove the two cap plugs located behind the
breaker door and to the right of the Main Breaker.
3. Loosen the lugs of the Main Breaker through the
access holes.
4. Insert a power wire (E1 or E2) through the opening
in the back cover and into the bottom lug. Torque to
the proper specification.
NOTE: There are three screws inside the top of the
breaker panel (behind the breaker door). Removing
these screws will allow the entire breaker box to be
carefully pulled out. When reinstalling, be certain that the
tabs on the bottom lock into place.
5. Connect the Neutral wire to the Neutral Lug if
applicable. Torque to the required specification.
See
Table 6-2.
6. Connect the Ground wire to the Ground Lug and
torque to the required specification. See
NOTE: Torque all wiring lugs, bus bars and connection
points to the proper torque specifications. Torque
specifications for the Main Line Circuit Breaker (MLCB)
can be found on a decal located on the inside of the Main
Line Circuit Breaker Door.

Battery Requirements

Group 26R, 12V, 540CCA (Minimum CCA)

Battery Installation

WARNING
WARNING
Fill the battery with the proper electrolyte fluid if
necessary and have the battery fully charged before
installing it.
Before installing and connecting the battery, complete the
following steps:
24
1. Verify that the generator has been turned OFF.
2. Turn off utility power supply to the transfer switch.
3. Remove the 7.5A fuse from the generator control
panel.
Battery cables were factory connected at the generator.
See Figure 6.2. Connect cables to battery posts as
follows:
Explosion. Batteries emit explosive gases.
Always connect positive battery cable first to
avoid spark. Failure to do so could result in
death or serious injury.
4. Connect the red battery cable (from starter
contactor) to the battery post indicated by a
positive, POS or (+).
5. Connect the black battery cable (from frame
ground) to the battery post indicated by a negative,
NEG or (-).
6. Install the red battery post cover (included).
NOTE: Dielectric grease should be used on battery
posts to aid in the prevention of corrosion.
Table
6-2.
NOTE: Damage will result if battery connections are
made in reverse.
A. Negative (-) Black lead from frame
B. Positive (+) Red lead from starter contactor
(000137a)
Figure 6-2. Battery Cable Connections
NOTE: In areas where temperatures fall below 32°F
(0°C), it is recommended that a pad type battery heater
be installed to aid in cold climate starting. This is
available as a cold weather kit through an authorized
service dealer.
(000138a)
Installation Guidelines For 50 Hz Air-Cooled Generators
WARNING
B
A
+
-
000621
(000133)