Descargar Imprimir esta página

Siemens SINAMICS G130 Manual De Listas página 921

Ocultar thumbs Ver también para SINAMICS G130:

Publicidad

PROFIBUS
PROFINET
PROFIdrive
receive telegram
Header
<3>
Drive object 1
Drive object 2
[2468], [2481]
.
r2090...r2095 bit
.
r2050[0...n] WORD
.
r2060[0...30] DWORD
...
Drive object n
Telegram assignment
.
according to p0922
.
[2420]
.
Drive object m
Trailer
<1> When selecting a standard telegram or a manufacturer-specific telegram via p0922, these interconnection parameters of the command data set CDS0 are automatically set.
<2> Data type according to to the PROFIdrive profile: I16 = Integer16, I32 = Integer32, U16 = Unsigned16, U32 = Unsigned32.
<3> Only for SINAMICS S120.
1
2
DO: A_INF, B_INF, CU_CX32, CU_G, CU_S, S_INF, SERVO, VECTOR
PROFIdrive - PZD receive signals, connection of manufacturer-specific
Signal receivers for PZD receive signals
Signal
Meaning
MOMRED
Torque reduction
MT_STW
Measuring probe control word
POS_STW
Pos control word
OVERRIDE
Pos velocity override
POS_STW1
Pos control word 1
POS_STW2
Pos control word 2
MDI_MOD
Pos MDI mode
M_LIM
Torque limit
M_ADD
Additional torque
E_STW1
Control word 1 for Active Infeed (ALM, SMART)
STW1_BM
Control word 1, variant for BM
STW2_BM
Control word 2, variant for BM
E_STW1_BM
Control word 1 for Active Infeed
CU_STW1
Control word 1 for Control Unit
3
4
<1>
PROFIdrive
Interconnection
Function
Signal No.
parameter
diagram
101
p1542
[5610.2]
130
p0682
-
203
(bitwise)
[2462]
205
p2646
[3630]
220
(bitwise)
[2463]
222
(bitwise)
[2464]
229
p2654
[3620]
310
p1503/p1552/p1554
-
311
p1495
-
320
(bitwise)
[2447]
322
(bitwise)
[2425]
324
(bitwise)
[2426]
326
(bitwise)
[2427]
500
(bitwise)
[2495]
5
6
Function diagram
fp_2440_54_eng.vsd
S120/S150/G130/G150
04.11.09 V04.03.01
PROFIdrive sampling time
Refer to [1020.7]
<2>
Data type
Normalization
I16
4000 hex
p2003
U16
U16
I16
4000 hex
100%
U16
U16
U16
U16
U16
U16
U16
U16
U16
U16
7
8
- 2440 -