Troubleshooting fuel oil

Check the following if failure occurs :
· power supply (power and control),
· fuel supply (valve pressure and
opening),
· control components,
· switch positions on TC control panel.
Symbol
Fault
w
Burner on safety lockout
Fan motor not working
contractor open
P
Fan motor not working
z
Fan motor working
1
No ignition arc
Electromagnetic valves not opening
Electromagnetic valves opening
electrically
Burner lights up, but flame is unstable
and goes out
Burner on continuous ventilation but no
I
flame
x
v
Other incidents
Sudden lockout at any time, not
indicated by any symbol
If problem persists :
· Check various program symbols
described here below on the control
and safety unit.
All the safety components must not be
repaired but only replaced by identical
components
m
Use only the manufacturer's
original parts
Cause
Parasitic flame on thermostatic cut-off
Faulty air pressure
Thermal relay cut out
Faulty contractor
Faulty wiring between contractor and motor
Faulty motor
Misadjusted or faulty air pressure switch
Faulty flame monitoring circuit
Ignition electrodes short-circuiting
Damaged ignition cables
Faulty ignition transformer
Control and safety unit
Electrical connections broken
Coil(s) short-circuiting
Mechanical jamming in valves
Fuel not getting through
Air flap too open and/or fuel oil flow too
high
Misadjusted combustion head
Faulty servomotor
Mechanical jamming of air flap
Faulty mechanical coupling
Premature flame signal
Old cell
11/2003 - Art. Nr. 13 013 506A
Note
After each operation :
· Check combustion and all circuits
for possible leaks.
· Perform safety check-up.
· Record results in the relevant
documents.
Corrective action
Check fuel valves for leaks
Fit a post ventilation device
Replace air pressure switch
Reset, adjust or change thermal relay
Change contractor
Check wiring
Replace motor
Adjust or replace air pressure switch
Check pressure pipes
Check if cell is clean
Change control and safety unit
Adjust or replace electrodes
Replace ignition cables
Replace ignition transformer
Change control unit
Check wiring between unit, servomotor and
motor pump
Change coil(s)
Change valve(s)
Check fuel oil level in tank, control valve and
pre filter opening
Check piping vacuum, spray pressure and
booster pump
Clean pump and pre filtering filter
Replace nozzles, pump, coupling, motor
pump motor and hoses
Adjust air flap and/or fuel oil flow rate
Adjust combustion head
Adjust or change servomotor
Unblock air flap
Check or change coupling
Change control and safety unit
Change cell