Alarms; Errors; Assistance: Setting The Parameters; Setting The Configuration Parameters - Friulinox BF030AG Manual De Uso, Mantenimiento E Instalación

Abatidor de temperatura

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

7.8. ALARMS

CODE
MESSAGE
A L
Minimum temperature alarm
AH
Maximum temperature alarm
Micro-port input alarm
i d
(only in "stand-by" mode and if
parameter i0 is set to 0 or 1)
Compressor protection input alarm
i A
(only if parameter i0 is set to 2)
When the cause that triggered the alarm has been resolved, the device restores normal operation.
To silence the buzzer, press any key while no procedure is in progress (the first press of the key does not cause the
associated effect).

7.9. ERRORS

CODE
MESSAGE
Cabinet probe error
P r 1
Pr 2
Pin probe error

7.10. ASSISTANCE: SETTING the PARAMETERS

7.10.1 SETTING THE CONFIGURATION PARAMETERS

The parameters are ordered on two levels
With no procedure in progress, the first level can be accessed by pressing
the display shows "PA".
Pressing
successively, the second level can be accessed:
- act on the
or
key to set "-19"
- press
to confirm, or do not operate
- press
and
for a few seconds: the display shows "CA1".
REMEDIES
Check the cabinet temperature
Check parameters A1 and A2
Check the cabinet temperature
Check parameters A3 and A4
Check the causes which activated the input
Check parameters i0 and i1
Check the causes which activated the input
Check parameters i0 and i1
REMEDIES
See P0 parameter
Check probe integrity
Check probe-device connection
Check the cabinet temperature
See P0 parameter
Check probe integrity
Check probe-device connection
Check the cabinet temperature
CONSEQUENCES
If the error occurs while in "stand-by" mode:
• if parameter C11 is set to 0, it will not be possible to start any of the cycles
• if parameter C11 is set to 1, the pin probe will function as the cabinet probe and only timed
cycles will be allowed to start
If the error occurs during a timed chilling operation:
• if parameter C11 is set to 0, the cycle will be interrupted
• if parameter C11 is set to 1, the pin probe will function as the cabinet probe and the chilling
operation will continue
If the error occurs during a set-temperature chilling operation:
• if parameter C11 is set to 0, the cycle will be interrupted
• if parameter C11 is set to 1, the pin probe will function as both the cabinet probe and pin
probe and the chilling operation will continue
If the error occurs during a storage operation:
• parameter C11 is set to 0, the compressor activity will depend on parameters C4, C5 and C6
• if parameter C11 is set to 1, the pin probe will function as the cabinet probe and the storage
operation will continue
If the error occurs while in "stand-by" mode:
• only timed operation cycles will be allowed to start
If the error occurs during a timed chilling operation:
• chilling will continue
If the error occurs during a set-temperature chilling operation:
• chilling will continue in timed mode
If the error occurs during storage mode:
• storage will continue
and
CONSEQUENCES
The device will continue to function normally
The device will continue to function normally
The outcome set by parameter i0
The compressor will be shut down
simultaneously and for a long period:
25 - EN