Table "A": Technical Data
EQUHI PF model
Fan coil application
Cooling capacity MIN/NOM/MAX (1)
Nominal cooling capacity (1) (*) EN 14511:2013
EER EN 14511:2013 (1) (*)
ESEER EN 14511:2013
Heating capacity MIN/NOM/MAX (2)
Nominal heating capacity (2) (*) EN 14511:2013
COP EN 14511:2013 (2) (*)
Application radiant
Cooling capacity MIN/NOM/MAX (3)
Nominal cooling capacity (3) (*) EN 14511:2013
EER EN 14511:2013 (3)
Heating capacity MIN/NOM/MAX (4)
Nominal heating capacity (4) (*) EN 14511:2013
COP EN 14511:2013 (4) (*)
Sound pressure (5)
Sound power (6)
Machine body sound power
Scroll compressor
Fans
Fan nominal air flow
Available static head
Maximum available static head
Heat exchanger water content
Water storage tank content
Heat exchanger nominal flow water side (1)
Residual head (P0/ASP0 installation) (1)
Residual head (PI0/ASPI0 installation) (1)
Residual head (P1/ASP1 mounting) (1)
Amount of R410A refrigerant
Amount of Oil PVE
Electrical data
Absorbed power in summer mode NOM (1) (●)
Absorbed power in winter mode NOM (2) (●)
Absorbed power in summer mode NOM (3) (●)
Absorbed power in winter mode NOM (4) (●)
Pump absorbed power (P0/PI0-ASP0/ASPI0)
Pump absorbed power (P1/ASP1)
Electrical power supply
Auxiliary power supply
Nominal current
Maximum current (■)
Pump absorbed current (P0/PI0-ASP0/ASPI0)
Pump absorbed current (P1/ASP1)
Dimensions
Width P0/PI0/P1
Width ASP0/ASPI0/ASP1
Height P0/PI0/P1
Height ASP0/ASPI0/ASP1
Depth P0/PI0/P1
Depth ASP0/ASPI0/ASP1
Water connections
(*) Under the following conditions: condenser
inlet air temperature 35°C; chilled water
temperature 7°C; temperature differential at
evaporator 5°C.
(2) In the following conditions: evaporator inlet
air temperature 7°C B.S., 6°C B.U.; hot water
temperature 45°C; temperature differential at
evaporator 5°C.
(3) Under the following conditions: condenser
inlet air temperature 35°C; chilled water
temperature 18°C; temperature differential at
evaporator 5°C.
(4) In the following conditions: evaporator inlet
air temperature 7°C B.S., 6°C B.U.; hot water
temperature 35°C; temperature differential at
evaporator 5°C.
IOM_EQUI PF-EQUHI PF_117a128_207983_200101_ES-EN-FR-DE-IT
(5) Sound pressure level in dB(A) referring to a
5 m distance from the unit, in directionality
factor equal to Q=2.
(6) Sound power level in dB(A) on the basis of
measurements taken in accordance with UNI
EN-ISO 9614 and Eurovent 8/1 Standards.
(■) Current drawn by the compressor and fans.
(●) Power absorbed by the compressor and
fans.
(*) The data according to EN14511 refer
staging P0/PI0/ASP0/ASPI0. Refer to the
section "Attachments Technical Note" to the
data of the establishment P1/ASP1.
97
117
kW
8,3/16/17
12/23,5/24,8
kW
16,2
2,98
4,26
kW
6,8/18,0/19,1 10,1/24,6/27,2
kW
17,7
3,32
kW
11/20,1/21,2 14,5/27,5/29,3 15,7/31,7/32,6
kW
20,3
3,86
kW
7,5/19,1/20,1 9,7/25,3/27,9 10,2/29,4/31,6
kW
18,8
4,10
dB(A)
53
dB(A)
77
dB(A)
68
Scroll regulated by inverter
n° x kW
1x0,814
m3/h
7600
Pa
80
Pa
800
l
1,5
l
110
l/h
2800
kPa
89/87
kPa
89/87
kPa
148/146
3,05
kW
5,6
kW
5,5
kW
5,4
kW
4,8
kW
0,3
kW
0,6
V-ph-Hz
400-3+N-50
V-ph-Hz
A
10,91
A
19,2
A
1,37
A
2,72
mm
1522
mm
1625
mm
1280
mm
1590
mm
835
mm
845
1 ½"
Ø
ESEER (European Sesonal EER) European
average seasonal efficiency.
ESEER+ with AdaptiveFunction Plus logic.
124
128
12,8/26,7/27,8
23,8
27,0
2,84
2,91
4,32
4,37
10,7/28,8/31
24,3
28,5
3,25
3,21
27,8
32,0
3,88
3,81
25,0
29,1
4,10
4,00
53
56
77
80
68
71
1x0,814
1x1,02
7600
8640
80
80
800
800
1,9
1,9
110
110
4000
4600
89/84
76/69
89/84
76/69
116/111
126/119
4,05
4,6
1,6
8,6
9,5
7,7
9,1
7,4
8,6
6,3
7,5
0,3
0,3
0,6
0,6
230-1-50
14,92
16,77
27,4
27,4
1,37
1,37
2,72
1,58
1522
1522
1625
1625
1280
1280
1590
1590
835
835
845
845
1 ½"
1 ½"