5.2 IO 351B
IO 351B
Module
Signal
Terminal Float switch
Analog inputs
AI1
51
IO 351B-1
AI2
54
Digital inputs
DI1
10
IO 351B-1
DI8
44
DI9
46
Digital outputs
DO1
77
DO2
79
DO3
81
DO4
82
IO 351B-1
DO5
84
DO6
86
DO7
88
Analog outputs
AO1
18
IO 351B-1
AO2
22
AO3
26
PTC inputs
PTC1
30
IO 351B-1
PTC2
32
2)
Connect either an energy meter or a flowmeter to the IO 351B-1 (DI1).
3)
See section Float switches.
Related information
5.3 Float switches
Description
The IO 351B is a general I/O module.
The IO 351B communicates with the CU 362 via
GENIbus.
Via the IO 351B inputs and outputs, the CU 362
controls the pumps according to the built-in
algorithms.
Analog sensor
User-defined
-
sensor 2
User-defined
-
sensor 3
Energy meter or
Energy meter or
2)
2)
flowmeter
flowmeter
3)
-
Float switch
3)
Float switch
-
Start of pump 1
Start of pump 1
Start of pump 2
Start of pump 2
All alarm relays
All alarm relays
VFD 1, reverse
VFD 1, reverse
VFD 2, reverse
VFD 2, reverse
-
-
User-defined
User-defined
alarms
alarms
VFD frequency,
-
pump 1
VFD frequency,
-
pump 2
-
-
PTC, pump 1
PTC, pump 1
PTC, pump 1
PTC, pump 1
Inputs and outputs
IO 351B inputs and outputs:
•
GENIbus communication (RS-485)
•
two analog inputs for connection to sensors
with current (0-20 mA/4-20 mA) or voltage
(0-10 V)
•
three analog outputs, 0-10 V, max. 2 mA
•
nine digital inputs
•
seven digital outputs, 240 VAC, 2 A
•
six PTC inputs.
Level control and safety
Analog sensor
Analog sensor
and safety float
and mixer
switches
User-defined
User-defined
sensor 2
sensor 2
User-defined
User-defined
sensor 3
sensor 3
Energy meter or
Energy meter or
2)
flowmeter
flowmeter
-
-
-
-
Start of pump 1
Start of pump 1
Start of pump 2
Start of pump 2
All alarm relays
All alarm relays
VFD 1, reverse
VFD 1, reverse
VFD 2, reverse
VFD 2, reverse
-
Mixer start
User-defined
User-defined
alarms
alarms
VFD frequency,
VFD frequency,
pump 1
pump 1
VFD frequency,
VFD frequency,
pump 2
pump 2
-
-
PTC, pump 1
PTC, pump 1
PTC, pump 1
PTC, pump 1
Analog sensor,
mixer and safety
float switches
User-defined sensor
2
User-defined sensor
3
Energy meter or
2)
2)
flowmeter
-
-
Start of pump 1
Start of pump 2
All alarm relays
VFD 1, reverse
VFD 2, reverse
Mixer start
User-defined alarms
VFD frequency,
pump 1
VFD frequency,
pump 2
-
PTC, pump 1
PTC, pump 1
13