Descargar Imprimir esta página

Grundfos CU 362 Instrucciones De Instalación Y Funcionamiento página 23

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 163
Example
1. Select input signal type, e.g. 4-20 mA.
2. Select input value, e.g. "Level, pressure".
3. Set sensor measuring range (minimum and maximum limits),
e.g. 0.0 to 5.0 m.
If an analog input is disabled, the display will only show
the upper part, i.e. the input setting.
If the input is enabled, "Measured input value" is shown. A
function can be linked to an analog input in another display. The CU
362 returns to the analog input setting display.
Path:Settings > I/O settings > Analog inputs > Analog inputs >
Analog inputs
Analog inputs, input value
The input value for the selected analog input is set in this display.
Path:Settings > I/O settings > Analog inputs > Analog inputs >
Analog inputs and measured value >
Analog inputs and measured value
6.4.2 Digital inputs
The digital input to be set is selected in this display.
As standard, there are 12 digital inputs. The display shows each
input so that its physical location can be quickly identified.
Example
The DI2 digital input on the IO 351B (designated terminal 12) is
linked to the function "Contactor feedback, pump 1", and the
contactor type is normally open.
DI1 (CU 362) [10] and DI2 (IO351B-41) [12].
Input
Control unit/module
DI1
CU 362
DI2
IO 351B
Path:Settings > I/O settings > Digital inputs >
Digital inputs
Digital inputs and functions
The signal input logic and the digital input function are set in this
display.
Path:Settings > I/O settings > Digital inputs > Digital inputs
and functions >
Terminal
10
12
23

Publicidad

loading