VALORES LÍMITES PARA EL AGUA DE ALIMENTACIÓN DE HUMIDIFICADORES DE ELECTRODOS SUMERGIDOS QUE FUNCIONAN CON AGUA
CON BAJO CONTENIDO EN SAL
Actividad hidrogeniones
Conductividad específica a 20 °C
Sólidos totales disueltos
Residuo seco a 180 °C
Dureza total
Dureza temporal
Hierro + Manganeso
Cloruros
Sílice
Cloro residual
Sulfato de calcio
(*) Valores dependientes de la conductividad específica; en general: c
LIMIT VALUES FOR THE SUPPLY WATER TO AN IMMERSED ELECTRODE HUMIDIFIER RUNNING
ON WATER WITH A LOW SALT CONTENT
Hydrogen ions
Specific conductivity at 20°C
Total dissolved solids
Dry residue at 180°C
Total hardness
Temporary hardness
Iron + Manganese
Chlorides
Silica
Chlorine residue
Calcium sulphate
(*) Values dependent on the specific conductivity; in general: c
La conexión de agua es de tipo G
Advertencia: no existe ninguna relación probada entre la dureza del
agua y la conductividad.
ADVERTENCIA IMPORTANTE: ¡No es necesario tratar el agua con
ablandadores! Esto puede provocar la formación de espuma, con un
potencial problema de funcionamiento irregular.
No se recomienda:
1. El uso de agua de pozo, de agua industrial o de agua procedente
de circuitos de refrigeración, en general, cualquier agua que pueda
estar contaminada química o bacteriológicamente;
2. la adición al agua de desinfectantes o de inhibidores de la corro-
sión, ya que son potencialmente irritantes.
≅ 0.65 * σ
R
3
/
M.
4
pH
-
σ
-
µS/cm
R, 20 °C
c
-
mg/l
R
R
-
mg/l
180
TH
-
mg/l CaCO
-
mg/l CaCO
-
mg/l Fe + Mn
-
ppm Cl
-
mg/l SiO
-
mg/l Cl-
-
mg/l CaSO
≅ 0,65 *σ
≅ 0,9 * σ
; R
R
R, 20 °C
180
pH
-
σ
-
µS/cm
R, 20 °C
c
-
mg/l
R
R
-
mg/l
180
TH
-
mg/l CaCO
-
mg/l CaCO
-
mg/l Fe + Mn
-
ppm Cl
-
mg/l SiO
-
mg/l Cl-
-
mg/l CaSO
≅ 0.9 * σ
; R
R, 20 °C
180
R, 20 °C
A G
3
/
M fitting is used for the water connection.
4
Note: no relationship can be demonstrated between the hardness and
the conductivity of the water.
IMPORTANT WARNING: the water does not need to be treated with
softeners! This may lead to the formation of foam, with potential
operating problems or anomalies.
The following are not recommended:
1. the use of well water, industrial water or water from cooling circuits
and, in general, any potentially chemically or bacteriologically
contaminated water;
2. the addition to the water of disinfectants or corrosion inhibiters,
as these are potential irritants.
13
Min
7
125
(*)
(*)
0
3
=
3
=
=
=
2
=
=
4
,
R
20 °C
Min
7
125
(*)
(*)
=
3
=
3
=
=
=
2
=
=
4
humiSteam - cod. +030221914 rel. 5.2 - 07.11.2005
LIMITES
Max
8,5
500
(*)
(*)
200
150
0,2
20
20
0,2
60
Tab. 3.1.2
LIMITS
Max
8.5
500
(*)
(*)
200
150
0.2
20
20
0.2
60
Table.3.1.2