Carel humiSteam Serie Manual Del Usuario página 67

Tabla de contenido

Publicidad

code displayed
controller
remote
causes
term.*
P
H
6 slow
E101
internal memory error
flashes
CAREL
or 4 fast
flashes
red
LED
Not
E112
error in the parameters user
featured
Not
E130
hour counter error
featured
not
E120
room probe not connected
featured
not
E123
outlet probe not connected
featured
not
E132
cylinder being depleted signal
featured
2 slow
E133
cylinder depleted signal
flashes
cylinder
red LED
9 slow
E134
cylinder full with machine off
flashes
signal
red LED
not
-
cleaning cylinder started signal
featured
not
E135
timeout signal (see parameter
envisaged
"bb") for maintenance
exceeded
not
E136
reached final limit (1.5xbb)
envisaged
of cylinder operating life
not
-
complete draining of the
envisaged
cylinder activated
not
-
complete draining for
envisaged
extended inactivity
not
-
complete periodical
envisaged
draining active
not
-
anti-foam algorithm
envisaged
active
* CAREL Humivisor (H or T)
** it is recommended to replace the cylinder first
Note:
for the P controllers the alarms cannot be reset. If the alarm is no longer active, it can only be reset by switching the machine off.
solution
1. reset the default parameters
(see Chap. 7.5)
2. if the problem persists, contact the CAREL down
service centre
1. with the machine off check that there
are no defective electrical connections
or faults, then reprogram the parameters
2. reset the default parameters
(see Chap. 7.5)
3. if the problem persists, contact the CAREL
service centre
with the machine off check that there are
no defective electrical connections or
faults, then reset the hour counter
(see par. 7.6)
check the connection of the probe,
parameter A2 for the room probe and the
setting of parameter A0 (see chap. 7)
check the connection of the probe,
parameter A6 for the outlet probe and the
setting of parameter A0 (see chap. 7)
perform maintenance and/or replace the
cylinder
perform maintenance and/or replace the
only
with the machine off:
1. check for any leaks from the fill
electrovalve or the condensate return
pipe
2. check that the level sensors are clean
total shut-down
see paragraph 6.2.1
perform maintenance and/or replace
the cylinder
replace the cylinder
see paragraph 6.3.2.6
see paragraph 11.4.5
see paragraph 11.4.9
see paragraph 11.4.3
67
action
reset
display (H)
P
H
total
machine
reprog.
shut-
disabled
by CAREL
-
machine
reprog.
disabled
params.
-
hour
reset
counter
manual
saving
hour
disabled
counter
-
machine
manual
disabled
-
signal
manual
only
-
signal
manual
only
signal
signal
not
only
available
total
machine
manual
shut-
disabled
down
-
-
-
-
signal
manual
only
reset
hour
counter **
-
disable
manual
unit
reset
hour
counter **
-
-
-
-
-
-
-
-
-
-
-
-
humiSteam - cod. +030221914 rel. 5.2 - 07.11.2005
alarm
reset
relay
relay (H)
active
reprog.
by
active
reprog.
params.
not
-
active
active
auto
active
auto
not
auto
active
not
-
active
active
manual
-
-
active
after the
manual
reset
hour
counter
active
after the
manual
reset
hour
counter
-
-
-
-
-
-
-
-
Table. 10.3.1