B.4 MAPA DE MEMORIA
Tabla B–9: MAPA DE MEMORIA DE MODBUS (Hoja 25 de 60)
DIR
NOMBRE DE REGISTRO
Third Harmonic Neutral Undervoltage (configuración agrupada de lectura/escritura)
6730
Third Harmonic Neutral Undervoltage Function
6731
Third Harmonic Neutral Undervoltage Pickup
6733
Third Harmonic Neutral Undervoltage Delay
6734
Third Harmonic Neutral Undervoltage Max Power
B
6736
Third Harmonic Neutral Undervoltage Min Power
6738
Third Harmonic Neutral Undervoltage Volt Supervision
6739
Third Harmonic Neutral Undervoltage Block
673A
Third Harmonic Neutral Undervoltage Target
673B
Third Harmonic Neutral Undervoltage Events
673C
Reservado (4 elementos)
Generator Unbalance (configuración agrupada de lectura/escritura)
6740
Generator Unbalance Function
6741
Generator Unbalance Source
6742
Generator Unbalance Source
6743
Generator Unbalance Stage 1 Pickup
6744
Generator Unbalance Stage 1 K value
6745
Generator Unbalance Stage 1 Tmin
6746
Generator Unbalance Stage 1 Tmax
6747
Generator Unbalance Stage 1 K Reset
6748
Generator Unbalance Stage 2 Pickup
6749
Generator Unbalance Stage 2 Pickup Delay
674A
Generator Unbalance Block
674B
Generator Unbalance Target
674C
Generator Unbalance Events
674D
Reservado (3 elementos)
Stator Ground Source (configuración agrupada de lectura/escritura)
6750
Stator Ground Source
Stator Ground (configuración agrupada de lectura/escritura)
6780
Stator Ground Function
6781
Stator Ground Stage 1 Pickup
6782
Stator Ground Stage 1 Pickup Delay
6783
Stator Ground Stage 1 Supervision
6784
Stator Ground Stage 2 Pickup
6785
Stator Ground Stage 2 Pickup Delay
6786
Stator Ground Stage 2 Supervision
6787
Stator Ground Block
6788
Stator Ground Target
6789
Stator Ground Event
678A
Reservado (5 elementos)
Split Phase Protection (configuración agrupada de lectura/escritura)
67A0
Split Phase Protection Function
67A1
Split Phase Protection Source
67A2
Split Phase Protection Load Source
67A3
Split Phase Protection Phase A Pickup
67A4
Split Phase Protection Phase A Offset
67A5
Split Phase Protection Phase A Slope
67A6
Split Phase Protection Phase B Pickup
67A7
Split Phase Protection Phase B Offset
67A8
Split Phase Protection Phase B Slope
67A9
Split Phase Protection Phase C Pickup
67AA
Split Phase Protection Phase C Offset
B-34
RANGO
0 a 1
0 a 30
0 a 600
0 a 30
0 a 30
0 a 1.25
0 a 65535
0 a 2
0 a 1
0 a 65535
0 a 1
0 a 5
0 a 1.25
0 a 100
0 a 100
0 a 50
0 a 1000
0 a 1000
0 a 100
0 a 1000
0 a 65535
0 a 2
0 a 1
0 a 65535
0 a 5
0 a 1
0 to 0.900
0 a 600
0.001 to 0.100
0 to 0.900
0 a 600
0.001 to 0.100
---
0 a 2
0 a 1
0 a 65535
0 a 1
0 a 5
0 a 5
0.020 a 1.500
0 a 1
0 a 100
0.020 a 1.500
0 a 1
0 a 100
0.020 a 1.500
0 a 1
Sistema de protección de generador G60
UNIDADES
PASO
FORMATO
---
1
F102
pu
0.0001
F003
s
0.01
F001
pu
0.001
F003
pu
0.001
F003
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
%
0.01
F001
---
0.01
F001
s
0.001
F001
s
0.1
F001
s
0.1
F001
%
0.01
F001
s
0.1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F167
---
1
F102
pu
0.001
F001
s
0.01
F001
pu
0.0001
F001
pu
0.001
F001
s
0.01
F001
pu
0.0001
F001
---
---
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F167
pu
0.001
F001
pu
0.001
F001
%
0.1
F001
pu
0.001
F001
pu
0.001
F001
%
0.1
F001
pu
0.001
F001
pu
0.001
F001
APÉNDICE B
PREDETERMINADO
0 (Desactivado)
3000
0
200
200
500
0
0 (restablecimiento
automático)
0 (Desactivado)
0
0 (Desactivado)
0 (SRC 1)
800
800
100
250
6000
2400
300
50
0
0 (restablecimiento
automático)
0 (Desactivado)
0
0 (SRC 1)
0 (Desactivado)
150
100
57
150
0
45
0
0 (restablecimiento
automático)
0 (Desactivado)
0
0 (Desactivado)
0 (SRC1)
0 (SRC1)
200
0
0
200
0
0
200
0
GE Multilin