NOTE: A 10-foot (3 m) section of pressure sensor cable is provided with the controller,
but it is possible to use similar 22 AWG wire for distances up to 100 feet (30 m) from the
pressure sensor. A 100-foot (30 m) section of pressure sensor cable is available from your
local Franklin Electric distributor. Low capacitance cable must be used if the pressure
sensor is being connected with cable not supplied by Franklin Electric. Cable length
longer than 100 feet (30 meters) should not be used as it can cause the drive to operate
incorrectly. (See Accessories section on page 36 for details.)
8. Verify that the SubDrive/MonoDrive unit is properly configured for the horsepower
rating of the motor and pump being used. (See the Pump Sizing section on page 18 for
information on Drive Configuration.)
9. Verify that the SubDrive/MonoDrive is correctly configured for the pressure sensor type
being used.
10. Replace the cover. Tighten screw to 10 in-lbs (1.1 Nm).
11. Connect the other end of the pressure sensor cable with the two spade terminals to the
pressure sensor. The connections are interchangeable.
12. Set the pressure tank pre-charge at 70% of the desired water pressure setting.
To check the tank's pre-charge, de-pressurize the water system by opening a tap with
the drive off. (See Table 4 on page 17.)
Measure the tank pre-charge with a pressure gauge at its inflation valve and make the
necessary adjustments.

Additional Control Input/Output Wiring

Built-In Duplex Alternator
The ALTERNATOR terminal supports the built-in Duplex Alternator function of the
SubDrive/MonoDrive Connect controllers. An appropriate Duplex Alternator communication
cable should be used to make the connection between both controllers using this terminal.
This Duplex Alternator cable leads should be wired to this terminal as follows:
(A): Black (same for both drives)
Both drives using the built-in Duplex Alternator function should be wired from the same
sub-panel to ensure proper communication and operation. See the Accessories section for
Duplex Alternator cable ordering information.

Moisture Sensor

The WET SENSOR terminal supports the Franklin Electric Moisture Sensor. The Moisture
Sensor leads should be wired to this terminal as follows:
(+24): Red
The (I+) and (I-) terminals accept an unpowered dry contact relay input and can be used
with other external control switches. Refer to the Advanced Setup section for more
information about configuring this input. See the Accessories section for Moisture Sensor
kit ordering information.
26
All manuals and user guides at all-guides.com
(B): Red (same for both drives)
( ): Black
(I+): White
( ): Green
(I-): Green