Descargar Imprimir esta página

Commands And Accessories - Roger Technology EDGE1/BOX Instrucciones Y Advertencias Para El Instalador

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 158
7

Commands and Accessories

If not installed, safety devices with NC contacts must be jumpered at the COM terminals, or disabled by modifying
the parameters
,
N.C. (Normally Closed).
CONTACT
13 (COR)
14
13 (COR)
14
16(+LAM)
15(COM)
17(+ES)
15(COM) Input for connecting electric lock, 12 Vdc max. 15 W
18(+24V)
15(COM) Power feed for external devices; see table "PRODUCT TECHNICAL FEATURES" on page 52
20(SC)
19(COM) Connection for gate open indicator lamp.
20(SC)
19(COM) Photocell test connection
22(FT2)
21(COM) Input (N.C. or 8.2 kOhm) for connecting photocells FT2
23(FT1)
21(COM) Input (N.C. or 8.2 kOhm) for connecting photocells FT1
24(COS2)
26(COM)
25(COS1)
26(COM) Input (NC or 8 kOhm) for connecting sensing edge COS1
58
,
,
,
and
.
DESCRIPTION
Output (potential free contact) for connecting courtesy light.
The COR output operating mode is managed by parameter
The voltage level of the battery can be set via parameter
The function of the electric lock is determined by parameter
Vmedia=12Vdc, Vmax=40Vdc; see table "PRODUCT TECHNICAL FEATURES" on page 52
The function of the indicator lamp is determined by parameter
Set the parameter
to enable the test function.
Each time a command is received, the control unit switches the photocells off and on to check that the
contact changes state correctly.
Power feeds for all external devices may be connected to reduce battery consumption (if batteries are
used). Set
or
.
WARNING! If contact 20 (SC) is used for the photocell test function or battery saving function, a gate
open indicator lamp cannot be connected.
The photocells FT2
. Photocell FT2 disabled when gate is opening.
. Photocell FT2 disabled when gate is closing.
. The gate opens when an open command is received if photocell FT2 is obstructed.
. NC (normally closed) incoming contact.
If the photocells are not installed, jumper the terminals 21(COM) - 22(FT2) or set the parameters
and
.
WARNING! Use R90/F4ES, G90/F4ES or T90/F4S series photocells.
The photocells FT1
. Photocell triggers only during gate closure. Photocell is ignored during gate opening.
. Movement is reversed if the photocell is triggered during gate closure.
. The gate opens when an open command is received if photocell FT1 is obstructed.
. NC (normally closed) incoming contact.
If the photocells are not installed, jumper the terminals 23(FT1) - 21(COM) or set the parameters
and
.
WARNING! Use R90/F4ES, G90/F4ES or T90/F4S series photocells.
Input (NC or 8 kOhm) for connecting sensing edge COS2.
. The sensing edge COS2 (NC contact) is disabled.
If the sensing edge is not installed, jumper the terminals 24(COS2) - 26(COM) or set the parameter
.
. If the sensing edge COS1 (NC contact) is enabled, the gate always reverses.
If the sensing edge is not installed, jumper the terminals 25(COS1) - 26(COM) or set the parameter
.
.
.
duty cycle
.
.
.
, while

Publicidad

loading

Este manual también es adecuado para:

Edge1/115/box