Instruction Manual TAP / Temperature And Pressure Gauge
Room temperature calibration
1. Turn off the TAP-CLAMP.
2. Place the TAP-CLAMP at constant temperature at 25 ± 3 °C con-
dition for 2 hrs. to ensure the temperature of the K – thermocou-
ple to be even.
3. While holding [UNIT], press [ON / OFF] until display shows
"CALL"
4. Release both buttons, the display shows "00"
5. Press [UNIT] button < 1 sec. to adjust the number to "09"
6. Press [ON / OFF] button < 1 sec. to show a code of temperature.
7. Wait the temperature code reading to be steady, press [ON /
OFF] button < 1 sec.
8. The display shows the ambient temperature.
9. Press [ON / OFF] button < 1 sec. to quit the temperature calibra-
tion.
Calibration of pressure gauge
Pressure calibration
Instruction Manual TAP / Temperature And Press
1. Turn off the TAP.
2. While holding [UP / MENU] button, press [ON / OFF] button, the
display shows "P-CALL"
3. Press [DOWN / SET] button until the display shows
"Password 00"
The TAP must not be used for anything other th
4. Press [UP / MENU] button shortly to adjust the number to
"Password 8"
5. Press [DOWN / SET] button until the display shows a reading
The TAP should not be exposed to moisture or
which is presenting the unload pressure. (i.e. 0.0 psi)
6. Press [DOWN / SET] awhile to enter calibration
Remove refrigerants from the TAP and the hos
Ensure all the refrigerant is exhausted from TAP valve or
connected hoses before performing calibration. The ac-
curacy will be affected due to the remaining refrigerant.
Purpose and use
7. While entering calibration, the display shows "400.0 psi". The
default pressure of calibration standard is 400 psi.
8. Press [UP / MENU] button shortly to select the calibration stan-
The TAP has been developed for measuring pressur
dard. The inlet pressure must be equal to the calibration stan-
and stationary refrigeration equipment.
dard pressure.
9. Press [DOWN / SET] awhile for calibration standard confirmati-
TAP is only designed for temporary measurement, d
on; the display shows the reading of unloaded pressure.
measurement unit.
10. Wait until the reading of unload pressure ist stable, pressuirze
400 psi (the inlet pressure must be equal to the calibration stan-
dard pressure). The display shows the corresponding pressure
Scope of delivery
value (i.e. 400.0 psi)
1 1. When the reading is stable, press [DOWN / SET] for confirmati-
on. Now the display shows "END"
Information about the various models and variations
12. Press [DOWN / SET] awhile to quit the pressure calibration.
REFCO catalogue or at www.refco.ch. The REFCO
Play Store.