2.4. AMBIENT TEMPERATURE AND AIR CIRCULATION
For air cooled refrigeration units, the air temperature in
the place of operation must not exceed 42°C. Declared
performance cannot be guaranteed if this temperature
is exceeded.
The remote condensation units must be installed in
special rooms or outdoors, protected against direct
sunlight. If circumstances make it necessary, the installer
must decide whether to provide a covering or shelter.
Sufficient air circulation must however be ensured.
For greater details
2.5. COOLING POWERS
Table 4
MODEL
Cooling yield [W]
C504
1807
C508
3614
C512
5421
Declared values at T.evap=-10°C and T.cond.=+40°C. Superheating in
accordance with EN12900.
2.6. ELECTRICAL CONNECTION
Up the line from each unit (cell and condensing unit) it
is obligatory to install an automatic circuit breaker in
compliance with the laws in force in the Country of
installation.
The power supply is to be carried to the electrical
panel of each single unit, as per the data in Table 5.
•
The electrical power cables must be properly sized
for the units installed;
•
The electrical cables must be placed and fastened in
the cable passage, and laid suitably for the place of
installation;
•
Each wire must be inserted to the corresponding
terminal.
•
The earth wire must be correctly connected to an
efficient earthing system.
All manuals and user guides at all-guides.com
see table 2.
Condensation power [W]
2748
5496
8244
Table 2
MINIMUM AIR CIRCULATION FOR CONDENSING UNITS
MODEL
C504
C508
C512
Table 3
MAXIMUM WATER CONSUMPTION FOR AIR COOLED CONDENSING UNITS
MODEL
Well water [l/h]
C504
C508
C512
Values referred to the declared condensation power at -10/+40°C in
accordance with EN12900.
Fig. 6
Fig. 7
9
M
3
/h AIR
1100
3000
4000
City water [l/h]
160
530
320
1050
480
1580