Menu
Item
2-9
Chilling set
3-1
Time of 1st defrost
3-2
Time of 2nd defrost
3-3
Time of 3rd defrost
Defrosting
3-4
Time of 4th defrost
parameters
3-5
Interval between 2 defrosts
3-6
Temperature at end of defrosting
3-7
Max. defrost time
Manual
4
defrosting
5-1
Cell temperature
5-2
Evaporator temperature
5-3
Ambient temperature
5-4
Low pressure
5-5
High pressure
Info
5-6
Working hours of compressor 1
5-7
Working hours of compressor 2
5-8
Working hours of compressor 3
5-9
Working hours of compressor 4
5-10
Status of the evaporator fan
Alarms
6
Display
Recordings
7
Print
Adjustment of parameter values:
Item
Name
2-1
∆t thaw alarm
2-2
Thaw alarm delay
2-3
Display of temp. in defrost
2-4
Duration of enhanced cycle
2-5
Time of door opening no. 1-2
2-6
Fan speed
2-7
Operating mode of relay of al. RL7
2-8
Frequency of recordings
2-9
Chilling set
3-1
time of 1st defrost
3-2
time of 2nd defrost
3-3
time of 3rd defrost
3-4
time of 4th defrost
3-5
Interval between 2 defrosts
3-6
Temp. at end of defrosting
3-7
Max. defrost time
CP+ = Conservation unit positive; CP- = Conservation unit negative; CPP+ = Conservation unit enhanced positive; CPP- =Conservation unit enhanced negative; CPCioK= CP Chocolate
All manuals and user guides at all-guides.com
Parameter
See tab.
"Parameter
Values"
See tab.
"Parameter
Values"
See tab.
"Parameter
Values"
See tab.
"Parameter
Values"
See tab.
"Parameter
Values"
See tab.
"Parameter
Values"
See tab.
"Parameter
Values"
See tab.
"Parameter
Values"
Range
1÷30°C
1÷30 min.
1-2-3
10 min.÷6 h
1÷30 min.
100÷40%
1-2-3-4
15 min.÷4 h
1F04÷1F03
00,10÷23,50
Par.3-1÷23.50
Par.3-2÷23.50
Par.3-3÷23.50
1÷24 h
1÷50°C
2÷99 min.
21
Value
Description
Temperature set for chilling during
enhanced cycle
Start the manual defrost cycle
Display the list of alarms
Insert the start and end date of the recordings
to be shown . Choose "Display" and the
recording will appear for the selected interval
Insert the start and end date of the
recordings to be printed. Select "Print" to
print the recordings of the selected interval
Default values
Resolution
CP Ciok
CP+
1°C
20°C
20°C
1 min.
20 min.
20 min. 20 min. 20 min. 20 min.
1
3
3
10 min.
NO
NO
1 min.
3 min.
3 min.
1%
100 %
100 %
1
3
3
15 min.
30 min.
30 min. 30 min. 30 min. 30 min.
0,1°C
NO
NO
10 min.
06,00
06,00
10 min.
23,50
23,50
10 min.
NO
NO
10 min.
NO
NO
1 h
12 h
12 h
1°C
6°C
6°C
1min.
6 min.
6 min.
CP-
CPP+
CPP-
20°C
20°C
20°C
3
3
3
NO
2 h
4 h
3 min.
3 min.
3 min.
100 %
100 %
100%
3
3
3
NO
0°C
-30°C
04,00
06,00
04,00
10,00
23,50
10,00
16,00
NO
16,00
22,00
NO
22,00
6 h
12 h
6 h
4°C
6°C
4°C
6 min.
6 min.
6 min.