RECESSED WALL MOUNT INSTALLATION
Recessed wall mount installation on models:
C255H / C256H / C355H / C356H / C505H / C506H
The maximum recess depth from rear of furnace forward
is 4 1/2-inches.
FIND THE STUDS AND CEILING JOINTS
Use a stud locater or small finishing nails. Repeatedly drive and
remove a nail into the wall in the area of the stud until it is located.
Then find the inside edge of the stud. Leave the nail at this location.
The other stud should be about 14 1/2-inches from the one found.
Drive finishing nails on the inside of this stud. Draw wall cutout to
required size as shown in Figure 5. If wall studs are not on 16-inch
centers. See "CLOSE OFF STUD SPACE." Figure 6
CUT WALL OPENING
Cut wall opening 14"-inches wide and 66"-inches high measured
from the top of the floor plate. Figure 5. All corners must be square.
INSTALLATION OF REAR OUTLET REGISTER
The optional rear outlet register may be installed when the furnace
is recessed into the wall. In new construction, install the rear outlet
plaster ground at the same time you install the header plate. For
existing construction, make the necessary cutout and install the
plaster ground before you install the furnace. See instructions packed
with accessory and Figure 5.
Do not allow wall finish material to project into the
furnace recess.
Do not install rear outlet register where grille may be blocked by a
door, curtains or any other obstruction.
GAS SUPPLY OPENING
A hole must be drilled for the gas line. Decide whether the gas line
will come through the floor or wall. Drill a 1 1/2-inch hole through the
floor or wall as needed. Figure 5.
CAUTION: Be careful not to damage any furnace components
while making any alternate hole.
INSTALLING YOUR FURNACE
FIGURE 5 - RECESSED WALL MOUNT INSTALLATION
B-W VENT
115.V OUTLET FOR
OPTIONAL BLOWER
8 1/8" X 13 1/4"
BASE PLATE
PLASTER TO TOP OF HEADER PLASTER GROUND
REAR REGISTER OPTIONAL FOR SINGLE
BURNER MODELS ONLY
9 1/8"
3 3/4"
PLASTER GROUND
NAIL FLANGE
CUTOUT
REAR
OUTLET
REGISTER
OPENING
14 3/8"
A = 4"
MODELS
20,500 &
35,000
ALTERNATE
BTU/HR.
GAS STUB
LOCATION
A = 2 5/8"
MODELS
50,000
BTU/HR.
2" x 4"
PLATE
66 1/8"
COZY TOP VENT GRAVITY GAS WALL HEATER
TOP OF HEADER
BOTTOM OF HEADER NAILING FLANGE
2" x 4" STUDS
TOP OF
HEATER
14 3/8"
2 X 4
FLOOR
PLATE
GAS STUB
LOCATION
FINISHED
FLOOR
11