Descargar Imprimir esta página

Wilo -Control EC-Drain LS1 Instrucciones De Instalación Y Funcionamiento página 13

Ocultar thumbs Ver también para Wilo-Control EC-Drain LS1:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 33
3 Transport and interim storage
Immediately after receiving the product:
• Check the product for damage in transit
• If damage is found, the necessary procedure
involving the forwarding agent must be taken
within the specified period.
CAUTION! Risk of damage!
Incorrect transport and interim storage can
cause damage to the product.
• The switchgear is to be protected against mois-
ture and mechanical damage.
• It must not be exposed to temperatures outside
the range –20 °C to +60 °C.
4 Intended use
The EC-Drain LS1 switchgear is for automatically
controlling a pump having up to max. P
power consumption
• in lifting units
• in sewage sumps
• for submersible pumps.
5.2
Technical Data
Mains supply voltage [V]:
Frequency [Hz]:
Max. rating [kW]:
Max. current [A]:
Protection class:
Max. fuse protection on mains side [A]:
Ambient temperature [°C]:
Alarm contact:
Housing material:
Housing dimensions:
Electrical safety:
5.3 Scope of delivery
• Switchgear EC-Drain LS1 (with built-in buzzer)
• Single-phase current (1~230 V) with shock-proof
plug
• Three-phase current (3~400 V) with CEE plug
• Installation and operating instructions
5.4 Accessories
Accessories must be ordered separately:
• Rechargeable battery (NiMH) 9 V / 200 mAh
• Horn 230 V / 50 Hz
• Flashing light 230 V / 50 Hz
• Signal lamp 230 V / 50 Hz
See the catalogue for a detailed list
6 Description and function
6.1 Product description (Fig. 1)
The EC-Drain LS1 is an electronic switchgear with
an integrated microcontroller.
It controls a pump depending on the switching
status of the connected float switch. When the
Installation and operating instructions Wilo-Control EC-Drain LS1
5 Product information
5.1 Type key
Example:
≤ 4.0 kW
EC
2
Drain
LS1
(1~)
1~230 V (L, N, PE)
3~400 V (L1, L2, L3, PE)
50/60 / Hz
P
≤ 4 kW, AC 3
2
12 A
IP 54
16 A, slow
-20 to +60 °C
Contact load max. 250 V~, 1 A
ABS
191 mm x 240 mm x 107 mm (WxHxD)
Degree of contamination II
DANGER! Danger of death!
The switchgear is not protected against explo-
sions and may not be operated in the explosive
area.
Always install the switchgear outside the explo-
sive area.
Correct use of the pump/installation also includes
following these instructions.
Any use over and beyond these is considered to be
incorrect use.
EC-Drain LS1 (1~)
Economy-Controller
Wastewater / sewage
Lifting station for 1 pump
(1~) = 1~230 V (L, N, PE)
(3~) = 3~400 V (L1, L2, L3, PE)
high water level is reached, optical and acoustic
signals are output and there is a forced pump
switch-on. The collective fault signal is active.
An optional rechargeable battery (accessory)
allows for a mains-independent alarm signal,
which signalises the missing mains voltage by
means of a continuous acoustic signal.
Pump faults are registered and evaluated.
The display of the operating states is signalised by
LEDs on the front side. Operation is done via but-
tons on the right side on the housing.
The switchgear is delivered for single-phase cur-
rent (1~230 V) with a shock-proof plug and an
integrated operating capacitor, or for three-phase
current (3~400 V) with a CEE plug with phase
inverter.
English
11

Publicidad

loading