Advanced Program Group
A110 [Anlg In 0-10V Lo]
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P034 [Minimum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value larger than A111 [0-10V Analog Input
High].
Values
Default
Min/Max:
Display:
P035 [Maximum Freq]
P034 [Minimum Freq]
0
0
A110 [Anlg In 0-10V Lo]
A111 [Anlg In 0-10V Hi]
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P035 [Maximum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value smaller than A110 [0-10V Analog Input
Low].
Values
Default
Min/Max:
Display:
A112 [Anlg In4-20mA Lo]
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P034 [Minimum Freq] if a 4-20mA input is
used by
P038
[Speed Reference].
Analog inversion can be accomplished by setting this value larger than A113 [4-20mA Analog Input
High].
Values
Default
Min/Max:
Display:
Programming and Parameters
(continued)
Related Parameter(s): d020, P034, P038,
0.0%
0.0/100.0%
0.1%
A111 [Anlg In 0-10V Hi]
Related Parameter(s): d020, P035, P038, A122,
100.0%
0.0/100.0%
0.1%
0.0%
0.0/100.0%
0.1%
Related Parameter(s): d021, P034,
3-31
A122
A123
P038