Installation/Wiring
Input/Output
3 Wire SRC Control -
Reversing
P036
[Start Source] = 1
A momentary input will
start the drive. A stop
input to I/O Terminal 01
will stop the drive as
specified by
P037
[Stop Mode]. I/O
Terminal 03
determines direction.
3 Wire SNK Control -
Reversing
Opto Output (1 & 2)
A058
[Opto Out1 Sel]
determines
Opto-Output 1 (I/O
Terminal 17) operation.
A061
[Opto Out2 Sel]
determines
Opto-Output 2 (I/O
Terminal 18) operation.
When using
Opto-Output with an
inductive load such as
a relay, install a
recovery diode parallet
to the relay as shown,
to prevent damage to
the output.
Connection Example
Internal Supply (SRC)
Stop
11
Start
Direction
Internal Supply (SNK)
Stop
Start
Direction
Opto-Output 1
17
CR
+24V
Common
Each Opto-Output is rated
30 VDC 50 mA (Non-inductive).
External Supply (SRC)
Stop
01
02
03
Start
Direction
+24V
Each digital input draws 6 mA.
01
02
03
04
09
01
02
03
04
Common