3-16
Programming and Parameters
A055
8 "Above DCVolt"
Options
(Cont.)
9 "Retries Exst"
10 "Above Anlg V"
11 "Logic In 1"
12 "Logic In 2"
13 "Logic 1 & 2"
14 "Logic 1 or 2"
15 "StpLogic Out"
16 "Timer Out"
17 "Counter Out"
18 "Above PF Ang"
19 "Anlg In Loss"
20 "ParamControl"
A056 [Relay Out Level]
32
32 bit parameter.
Sets the trip point for the digital output relay if the value of
18 or 20.
A055 Setting
6
7
8
10
16
17
18
20
Values
Default
Min/Max:
Display:
• Drive exceeds the DC bus voltage value set in
[Relay Out Level].
• Use A056 to set threshold.
Value set in
• Analog input voltage (I/O Terminal 13) exceeds the value
set in
A056
• Do not use if
In".
• This parameter setting can also be used to indicate a PTC
trip point when the input (I/O Terminal 13) is wired to a
PTC and external resistor.
• Use A056 to set threshold.
An input is programmed as "Logic In 1" and is active.
An input is programmed as "Logic In 2" and is active.
Both Logic inputs are programmed and active.
One or both Logic inputs are programmed and one or both is
active.
Drive enters Step Logic step with Digit 3 of Command Word
(A140
- A147) set to enable Step Logic output.
• Timer has reached value set in
• Use A056 to set threshold.
• Counter has reached value set in
• Use A056 to set threshold.
• Power Factor angle has exceeded the value set in
[Relay Out Level].
• Use A056 to set threshold.
Analog input loss has occurred. Program
Loss] for desired action when input loss occurs.
Enables the output to be controlled over network
communications by writing to
(0 = Off, 1 = On.)
A056 Min/Max
0/400 Hz
0/180%
0/815 Volts
0/100%
0.1/9999 Secs
1/9999 Counts
1/180 degs
0/1
0.0
0.0/9999
0.1
A092
[Auto Rstrt Tries] is exceeded.
[Relay Out Level].
A123
[10V Bipolar Enbl] is set to 1 "Bi-Polar
A056
Related Parameter(s): A055, A058,
A055
[Relay Out Sel] is 6, 7, 8, 10, 16, 17,
A056
A056
[Relay Out Level].
A056
[Relay Out Level].
A056
A122
[Analog In
[Relay Out Level].
A061