Gram IF 4000 Manual De Uso página 249

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3-22
Programming and Parameters
Advanced Program Group
Stop drive before changing this parameter.
A095 [Reverse Disable]
Enables/disables the function that allows the direction of motor rotation to be changed. The reverse
command may come from a digital command, the keypad or a serial command. All reverse inputs
including two-wire Run Reverse will be ignored with reverse disabled.
Options 0 "Reverse Enabled"
(Default)
1 "Reverse Disabled"
A096 [Flying Start En]
Sets the condition that allows the drive to reconnect to a spinning motor at actual RPM.
Options 0 "Disabled" (Default)
1 "Enabled"
A097 [Compensation]
Enables/disables correction options that may improve problems with motor instability.
Options 0 "Disabled"
1 "Electrical" (Default)
2 "Mechanical"
3 "Both"
A098 [SW Current Trip]
Enables/disables a software instantaneous (within 100 ms) current trip.
Values
Default
Min/Max:
Display:
A099 [Process Factor]
Scales the value displayed by d010
Output
Process
=
x
Freq
Factor
Values
Default
Min/Max:
Display:
0.0 (Disabled)
0.0/(Drive Rated Amps × 2)
0.1 Amps
[Process
Display].
Process
Display
30.0
0.1/999.9
0.1
(continued)
Related Parameter(s):
d010

Publicidad

Capítulos

Tabla de contenido
loading

Productos relacionados para Gram IF 4000

Tabla de contenido