NAME
dt2
Condenser defrost termination timer (minutes)
Increments of 5 minutes.
Timer will count from defrost mode initiation. Timer will reset after a temperature defrost termination or timer time out. On time out the unit will switch from defrost
to null mode.
When the value is set at 0, is the test position: the defrost will stop in 15 seconds.
EFc
Evaporator Fans constant blow
on: evaporator fans stays on also during null mode.
off: the evaporator fans remain off in Null mode.
dAL
Out of range alarm
Progammable from 1º up to 10º or off (0). When the difference between the return air temperature and the set point exceeds the on-screen return air temperature
reading flashes.
HC
Hour Counter initial value for maintenance purposes
(tens of hours, e.g. 150=1500 hours), programmable from 1000 up to 5000, 500 steps.
dSP
doors Switches Presence/Polarity
0: normally closed, 1: normally open, 2: not present.
bE
buzzer Enable
0: not enabled, 1: enabled, 2: enabled also when keys are pressed, 3: enabled only when keys are pressed.
tu
thermostat units
C: temperature visualization in ºC, F: temperature visualization in ºF.
Pu
pressure units
b: pressure visualization in bar, P: pressure visualization in psi.
trE
Temperature display resolution
0: whole; 1: resolution 0.5; 2: resolution: 0.1
DESCRIPTION
DEFAULT
MIN
MAX
45
5
50
OFF
OFF
ON
0
0
10
150
0
500
1
0
2
2
0
3
C
C
F
P
b
P
0
0
2
41