1.1 - GUIDELINES ON ELECTRICAL CONNECTIONS
Prepare cable ducts on the installation site.
The cables for the connection of the various devices in a typical plant are listed in the table below and must be suitable for the type
of installation, for example we recommend a cable type H07RN-F for outdoor installation.
CONNECTION
Power line
Flashing
Photocell - transmitter
Photocell - receiver
Key selector
Only use the supplied connectors:
CLAMP POSITION
All
The following table shows the type and size of the allowable cables for the screw terminals of the above type and the closing torques:
mm
6.5
in.
0.26
mm
0.2 ... 2.5
2
AWG
24 ... 14
Use copper conductors (mandatory).
Avoid the presence of exposed copper wires or coming out of the clamp.
6-1622467M - rev. 1 - 07/03/2024
CABLE
3 x 1,5 mm²
3 x 2,5 mm²
3 x 3,5 mm²
2 x 0,5 mm²
2 x 0,5 mm²
4 x 0,5 mm²
4 x 0,5 mm²
PHOENIX BCP-500-2GN
0.2 ... 2.5
0.25 ... 2.5
24 ... 14
24 ... 14
Ø 3.5 mm (0.14 in.)
LENGTH
< 10 m
10 ÷ 50 m
> 50 m
< 20 m
< 20 m
< 20 m
< 20 m
TYPE CLAMP
2 x 0.2 ... 0.75
2 x 0.2 ... 0.75
24 ... 14
2 x 24 ... 18
Translated from the original language - English - 5
2 x 0.25 ... 0.75
2 x 0.25 ... 0.75
2 x 24 ... 18
2 x 24 ... 18
N • m
0.5
Ib-in
4.5
2 x 0.5 ... 1.5
2 x 20 ... 16