Descargar Imprimir esta página

HR Matic BIOS1 RNS HR Serie Manual De Instalacion Y Uso página 68

Publicidad

Idiomas disponibles

Idiomas disponibles

Configuration of the flashing output
Customize the behavior of the flashing output according to the type of connected device.
PARAMETER
FPr
Flashing time before handling
Set how long the flashing output is activated before starting handling.
PARAMETER
tPr
Courtesy light output configuration
Customize the mode of action of the courtesy light output.
Value 0: The light goes out at the end of a maneuver, after waiting for the time set in the parameter tCY.
Value 1: The light turns off at automation in the position of "CLOSED GATE", after waiting for the time set in the parameter tCY.
Value 2: With each command received, the light remains lit only for the time set in the tCy parameter regardless of the position
where the gate is located.
Value 3: Open automation light function. The light turns off when the automation reaches the position of "CLOSED GATE".
Value 4: Open automation indicator function with blink proportional to the state of the automation. In detail:
Opening movement = slow flashing.
Closing movement = fast flashing.
Position of "OPEN GATE" = light on.
Position of "CLOSED GATE" = light off.
Gate stopped in intermediate position = alternates two flashes and a long pause.
PARAMETER
FCy
Time for courtesy light
Set a time to activate or wait for the courtesy light. To be used in combination with the parameter "Courtesy light output configu-
ration".
PARAMETER
tCY
30 - English - Translated from the original language
VALUES
0 = Flashing light with self-flashing circuit
1 = Flashing without self-flashing circuit
VALUES
OFF = disabled
from 1 to 10 seconds
VALUES
0 = light on during operation + TCY
1 = light off in "CLOSED" after TCY
2 = light on for TCY
3 = open gate spy
4 = proportional flashing
VALUES
OFF = disabled
from 1 to 900 seconds
DEFAULT
1
DEFAULT
OFF
DEFAULT
0
DEFAULT
180 seconds
6-1622467M - rev. 0 - 07/03/2024

Publicidad

loading

Este manual también es adecuado para:

Bios1 230v rns hrBios1 120v rns hr