Auto-test function of the EDGE input
• Activation of the EDGE input auto-test function contributes to the achievement of safety standards
throughout the connected control line. Refer to the instruction manual of the connected device for the
degree of safety achieved.
• To use this function correctly it is necessary to connect a device with electronic test circuit (e.g. R.CO.O).
Connect the device test contact to terminal 8 of the control unit, and enable the test with the low logic level
0Vdc.
By enabling this function, the control unit performs a functional test of the safety edge before each handling. The test, if enabled, is
not performed in case of fast reversals (for example, reversal caused by the intervention of a photocell).
PARAMETER
tEd
Amplitude of the partial opening
Adjusts the amplitude of the partial opening as a percentage of the total stroke length.
Partial opening is possible only starting from the position of "CLOSED GATE", using the appropriate command. Once reached the
position of "PARTIAL OPENING" the display shows " PE ".
PARAMETER
LPo
Automatic Closing from Partial Opening
Set a waiting time before the control unit controls an automatic closing after reaching the "PARTIAL OPENING" position.
Once reached the position of "PARTIAL OPENING" the control unit starts the countdown by displaying on the screen "-tp" (the
symbol "-" is replaced by a number in the last 10 seconds of the countdown).
In case the photocell input is active the countdown stops until the contact is restored.
PARAMETER
tPC
6-1622467M - rev. 1 - 07/03/2024
WARNING
VALUES
OFF = disabled
ON = enabled
+24V
GND
17
R.CO.O
VALUES
OFF = disabled
from 1 to 100 % of total length
VALUES
OFF = disabled
from 1 to 900 seconds
NOTE
+24V
TEST
EDGE
18
19
20
DEFAULT
OFF
21
DEFAULT
30 %
DEFAULT
OFF
Translated from the original language - English - 29