Signal sources for E_DIGITAL for telegram 390
Signal
Meaning
E_DIGITAL.0
CUD digital input 4 (DI 4)
E_DIGITAL.1
CUD digital input 5 (DI 5)
E_DIGITAL.2
CUD digital input 6 (DI 6)
E_DIGITAL.3
CUD digital input 7 (DI 7)
E_DIGITAL.4
Reserved
E_DIGITAL.5
Reserved
E_DIGITAL.6
Reserved
E_DIGITAL.7
Reserved
E_DIGITAL.8
CUD digital input 0 (DI 0)
E_DIGITAL.9
CUD digital input 1 (DI 1)
E_DIGITAL.10
CUD digital input 2 (DI 2)
E_DIGITAL.11
CUD digital input 3 (DI 3)
E_DIGITAL.12
Reserved
E_DIGITAL.13
Reserved
E_DIGITAL.14
Reserved
E_DIGITAL.15
Reserved
<1> Default can be changed by user.
<2> This interconnection will not be established automatically by setting of p0922 =390. If required the interconnection must be established by the user.
1
2
DO: CU_DC
PROFIdrive - E_DIGITAL interconnection
<1>
Interconnection
parameter
CU_DC DC_CTRL
<3>
<2>
p2082[0] = r53010.8
CU_DC DC_CTRL
<3>
<2>
p2082[1] = r53010.10
CU_DC DC_CTRL
<3>
<2>
p2082[2] = r53010.12
CU_DC DC_CTRL
<3>
<2>
p2082[3] = r53010.14
CU_DC DC_CTRL
<2>
p2082[8] = r53010.0
CU_DC DC_CTRL
<2>
p2082[9] = r53010.2
CU_DC DC_CTRL
<2>
p2082[10] = r53010.4
CU_DC DC_CTRL
<2>
p2082[11] = r53010.6
3
4
Function diagram
Inverted
[2060.8]
[2060.8]
[2065.8]
[2065.8]
[2050.7]
[2050.7]
[2050.7]
[2050.7]
<3> Can be set via p50789[0…3] as digital input or digital output.
5
6
fp_2498_13_eng.vsd
16.11.18 V01.05.00
PROFIdrive sampling time
7
8
Function diagram
- 2498 -