Htsk temp type
Temp_sensor 1
0...2
p51830[0] (0)
Temperature sensor 1
XT5
<1>
T
#
XT5:
Device with thyristor modules:
Temperature sensor in main heat sink.
Device with disc-type thyristors:
No temperature sensor connected.
Temp_sensor 2
p51830[1] (0)
Temperature sensor 2
XT6
<1>
T
#
XT6:
For option L15:
Sensor is mounted in the cooling air
intake of the unit.
Temp_sensor 3
p51830[2] (0)
Temperature sensor 3
XT7
<1>
T
#
XT7:
terminal (reserved).
Temperature sensor on
gating module
T
#
Depending on the MLFB, the devices are equipped with one or more temperature sensors - see r52049.0..3.
<1> This parameter is only effective with the Control Module, otherwise a fixed value is used.
<2> The display parameters for temperature sensors that are not present return an invalid value (e.g. -200 °C).
The temperature sensors are monitored for wire breaks and F60096 is triggered if necessary.
1
2
DO: DC_CTRL
Signals and monitoring functions - Device-internal monitoring functions
Htsk temp thresh
<1>
Temp_sensor 1
0.0...200.0 [°C]
p51829[0] (90.0)
1
Temp sensor disp
0
+
Temp 1 [%]
<2>
[8042.1]
5 °C
r52050[0]
[8047.1]
1
Temp sensor/Mod
<2>
Temp sensor 1 [°C]
0
r50013[0]
<1>
Temp_sensor 2
p51829[1] (90.0)
1
0
+
Temp 2 [%]
<2>
[8042.1]
5 °C
r52050[1]
[8047.1]
1
<2>
Temp sensor 2 [°C]
0
r50013[1]
<1>
Temp_sensor 3
p51829[2] (90.0)
1
0
+
Temp 3 [%]
<2>
5 °C
r52050[2]
[8047.1]
1
<2>
Temp sensor 3 [°C]
0
r50013[2]
Threshold
1
0
+
Temp gating mod [%]
<2>
5 °C
r52050[3]
1
<2>
Temp gating mod [°C]
0
r50013[3]
3
4
Supply voltage
F60067
"Fault
P5/P15
temperature too high"
P5
A60080
"Alarm
temperature too high"
P15
F60067
"Fault
P24
temperature too high"
A60080
P10
"Alarm
temperature too high"
F60067
"Fault
temperature too high"
N10
A60080
"Alarm
temperature too high"
F60067
"Fault
temperature too high"
A60080
"Alarm
temperature too high"
Temperature sensor on
CUD Control Unit
5
fp_8048_13_eng.vsd
31.10.18 V01.05.00
F60097
"Power supply faulty"
F60093
"Power supply P5
overloaded"
F60094
"Power supply P15
overloaded"
F60091
F60095
"Reference voltage P10
"Power supply P24
outside tolerance"
overloaded"
Deviation > ±5 %
Electr supp V disp
u
P10 (+10 V)
#
r50823[0]
F60092
"Reference voltage N10
outside tolerance"
Deviation > ±5 %
Electr supp V disp
u
N10 (-10 V)
#
r50823[1]
t
Electr supp t_fail [ms]
#
r50824
95 °C
F60090
1
"Fault
0
module temperature exceeded"
90 °C
A60081
1
"Alarm
0
module temperature exceeded"
Temp CUD control u [%]
<2>
T
r52050[4]
#
<2>
Temp CUD control u [°C]
r50013[4]
6
7
Function diagram
SINAMICS DCM
8000 μs
8
- 8048 -