Descargar Imprimir esta página

Siemens SINAMICS DCM Manual página 842

Ocultar thumbs Ver también para SINAMICS DCM:

Publicidad

1
2
DO: DC_CTRL
Signals and monitoring functions - Motor interface (part 2)
10 s
Mot br l sig s
p50486
T
0
(0)
2 s
Mot brg cond sig s
p50487
T
0
(0)
40 s
Mot mot fan sig s
p50488
T
0
(0)
10 s
Mot mot temp sig s
p50489
T
0
(0)
3
4
F60025
"Brush length too short"
Br_l too short
r53120.0
F60026
"Poor bearing condition"
Poor bearing cond
r53120.1
F60027
"Motor fan fault"
Mot fan F
r53120.2
F60028
"Motor temperature too high"
Mot_temp too high
r53120.3
5
6
fp_8035_13_eng.vsd
10.08.18 V01.05.00
8000 μs
7
8
Function diagram
- 8035 -
SINAMICS DCM

Publicidad