Temperature
Hardware
sensor
smoothing
+ temp
(1 s)
X522.7
2 mA
+
X522.8
-
KTY/PTC/
- temp
PT1000
<1> p4100
= 0: Evaluation disabled
= 1: PTC
= 2: KTY
= 6: PT1000
<2> An alarm A35920 in the temperature evaluation of the TM31 is signaled to the next (downstream) vector control via the special temperature
value -300 °C.
<3> As a result of the wire breakage monitoring the maximum temperature that can be measured is limited to approximate 188.6 °C.
<4> PTC:
A value > 250 °C de-activates the alarm or fault.
KTY/PT1000: A value > 188.6 °C de-activates the alarm or fault.
<5> PTC:
p4103 = 0
delay time = 0 s.
KTY/PT1000: p4103 = 0
Output from temperature timer even off (0).
1
2
DO: TM31
Terminal Module 31 (TM31) - Temperature evaluation
1650 Ohm (PTC)
PTC
R_sensor
r4101
Sensor type
p4100 (0)
Software
smoothing
<1>
(0.5 s)
A
KTY
Calculate
resistance
D
PT1000
3
4
-50 °C 250 °C
0
1
1
0
<1>
Alarm threshold
Sensor type
-48...251 [°C]
p4100 (0)
p4102[0] (100)
-300 °C
<3>
0
188.6 °C
1
R
2
6
T
-140 °C
Fault threshold
<3>
-48...251 [°C]
188.6 °C
p4102[1] (120)
R
T
-99 °C
Measured temperature
Alarm is present
-300 °C
5
6
fp_9576_51_eng.vsd
04.12.12 V01.05.00
p4099[0] (4000.00 μs)
A35211
0.000...600000 [ms]
<4>
Alarm is present
p4103 (0.000)
r4104.0
<5>
1
T
0
0
5 K
1
F35207
Fault is present
r4104.1
<4>
1
0
5 K
A35920 "Error temperature sensor channel 0"
<2>
0
TM31 temp act val
r4105
1
7
Function diagram
SINAMICS
8
- 9576 -