Settings On The Measurement Devices; Making General Settings On Measurement Devices - SMA FUEL SAVE CONTROLLER 2.0 Instrucciones De Uso

Ocultar thumbs Ver también para FUEL SAVE CONTROLLER 2.0:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SMA Solar Technology AG
Parameter
Description
Nominal droop
Power alteration proportionate to
frequency
the nominal power of the battery
inverter in the event of deviation
from the mains nominal fre-
quency
Upper SOC op-
Maximum battery state of charge
erating limit
If the maximum battery state of
charge has been exceeded, the
battery is no longer charged with
electrical energy.
Lower SOC op-
Minimum battery state of charge
erating limit
If the battery state of charge falls
below the minimum value, no
more electrical energy is supplied
from the battery.
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Choose the menu Configuration Wizard via the page and menu selection.
2. In the Battery system bar, select the [Adjust] button.
3. Set the parameters in the Battery general configuration and Battery controller configuration sections (see
Section 4.8.3, page 20).
4. To continue with system settings, select the [Continue wizard] button.
5. Select the [Done] button.
6. Activate monitoring for the state-of-charge limits Upper SOC operating limit and Lower SOC operating limit
(see Section 8.3.1, page 84).
7. End the system settings (see Section 7.9.1, page 67).
7.5

Settings on the Measurement Devices

7.5.1

Making General Settings on Measurement Devices

The system settings of the Fuel Save Controller can only be adjusted when the Fuel Save Controller is in STANDBY or
ERROR mode. The operating state STANDBY can be reached by stopping the SMA Fuel Save Controller.
User Manual
Value
Explanation
0% to 200%
0% to 100%
0% to 100%
7 System Settings
Default
value
100 %
100 %
0 %
FSC20-BA-xx-20
55

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido