SMA Solar Technology AG
8.4.2
Options for Specifying the Reserve Power Setpoint of the Gensets
Parameter overview
Figure 43: Genset Setpoints: Specification of setpoints for gensets
Parameter
Description
GenSpntTrigPctNeg
The reserve power setpoint will be transmit-
ted immediately to the genset system if a neg-
ative change of the setpoint is greater than
this percentage of the connected nominal
Genset power.
GenSpntTrigPctPos
The reserve power setpoint will be transmit-
ted immediately to the genset system if a pos-
itive change of the setpoint is greater than
this percentage of the connected nominal
Genset power.
GenSpntTrigTm
The reserve power setpoint for the Genset
system will be transmitted /n cyclical after
this time in seconds.
Requirement:
☐ You must be logged in as Installer.
User Manual
Value
Default value
0% to 10000%
20 %
0% to 10000%
20 %
0.1 s to 3600 s
120 s
FSC20-BA-xx-20