8 System Control
Parameter
Description
GenCosPhiWarnTm
Warning timer for cosPhi opera-
tion of Gensets
GenCosPhiWarnUx
Warning threshold of cosPhi for
underexcited operation of
gensets
* When the function Reactive Power Management is activated, the function Reactive Power Control must be deactivated (see
Section 8.2.1, page 77).
Figure 37: Reactive Power Management: Settings regarding the reactive power of the PV power plant (continued)
Parameter
Description
GridCosPhiWarnOx
Warning threshold of cosPhi for
overexcited operation of grid
GridCosPhiWarnUx
Warning threshold of cosPhi for
underexcited operation of grid
GridCosPhiWarnTm
Warning timer for cosPhi opera-
tion of grid
FixedCosPhiBat
Fixed cosPhi in grid operation
(only active if selected in Rpm-
GridMode)
82
FSC20-BA-xx-20
Value
Explanation
0 s to 86400 s
-1 to 0
Value
Explanation
0 to +1
-1 to 0
0 s to 86400 s
0 to 1
SMA Solar Technology AG
Default
value
10.0 s
-0.800
Default
value
0.700
-0.700
10.0 s
0.900
User Manual